Information: Power Modules (Rectifiers)
Rectifiers
Rectifier
Input V
AC
Option
Output DC (nominal)
Voltage
Power
gray
IP020ACR125ATEZ
125Vdc
200
-
277 Vac
AC, L3, HW
125Vdc
2500W
100
-
120 Vac
AC
125Vdc
1280W
blue
IP050ACR048ATEZ
48Vdc
200
-
277 Vac
AC, L3, HW
48Vdc
2725W
100
-
120 Vac
AC
48Vdc
1200W
orange
IP100ACR024ATEZ
24Vdc
200
-
277 Vac
AC, L3, HW
24Vdc
2725W
100
-
120 Vac
AC
24Vdc
1200W
gray
IP040H3R125ATEZ
125Vdc
320
-
530 Vac
H3
125Vdc
6000W
Rectifier LEDs
Power Unit LEDs
LED
Description
Norm
Normal—Green
ACF
AC Input Failure—Red
Fail
Failure—Red
RP
Reverse Polarity Failure—Red
Maintenance
-
Air Filters
Air Filters should be washed or replaced at intervals determined by the installation environment—dusty
environments require more frequent service.
Air filters may be washed and reused.
1.
Remove air filter carrier—
2
thumb screws.
2.
Remove and replace air filter.
Air filter slides out to the rear of the air filter carrier.
3.
Replace air filter carrier with filter—secure with 2 thumb screws.
Filter Washing
1.
Wash filter in soap water.
2.
Gently wring out by hand.
3.
Air dry for at least 24 hours before installing into filter