![ABB Integritas Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/abb/integritas/integritas_quick-start-manual_4116003022.webp)
QUICK START GUIDE
Page 22
Version 6.0
© 2021 ABB. All rights reserved.
Battery Temperature Measurement
Ordering Codes
Descriptions
1600093513A
DTP873
-
Battery Thermal Probe
1600093512A
DTP873
-
Ambient Probe
Information Interlock Cable Recommendations
•
Wire
-
20
-
24 AWG
•
Mating Connector: Molex housing
-
43025
-
0200,
•
Terminals
-
Molex 43030
-
0008 (15µ
”
gold plated)
•
Hand Crimp Tool
-
Molex 0638190000
•
Insertion Tool
-
Molex 0638120800
•
Extraction Tool
-
Molex 0011030043
Information: Signal Connections.
Alarm Relays Factory set to Open On Alarm. Rated 125V (60V for 24V and 48V chargers), 0.5A.
“
Dry
”
No Voltage Binary Inputs Require a contact closure to Common (pin 2).
“
Dry
”
24V Biased Binary inputs Require a contact closure to 24V Source (pin 2).
Pulsar XL Alarm Outputs
Connector
Description—Signal on Pin 1
Pin 2
TB1
Power Critical Alarm
Common
TB2
Power Major Alarm
Common
TB3
Power Minor Alarm
Common
TB4
Alarm R1 (default is RFA/MRFA)
Common
TB5
Alarm R2 (default is ACFMACF)
Common
TB6
Alarm R3 (default is BD/VLV)
Common
TB7
Alarm R4 (default is GFI)
Common
TB8
Alarm R5 (default is SPD, DC, and AC)
Common
TB9
Alarm R6 (default is BTA
“
Battery Test Active
”)
Common
TB10
Alarm R7 (default is
“
Check Battery
”)
Common
Information: Battery Monitoring Connections
-
for use with NiCd and Lead acid
batteries (VRLA, Flooded)
Battery Monitoring is accomplished with a
“
Daisy Chained
”
series of probes. The Probes monitor battery
temperature. Bolt the Probe under the
“
–
“
terminal connector hardware; NOT under the connecting lug.
Max per system: Probes
-
16.