Adding Alarm and Event Handling
Section 4 Engineering
56
3BSE040587R4401
12. A warning for unresolved references will appear. This because of the
unconfigured remaining buttons. Neglect the warning and click OK. Another
option is to remove the unconfigured buttons.
13. You have now created a faceplate, with a button that sets a property in the PLC.
14. Close the window.
15. Set the faceplate to default aspect:
a.
Open the faceplate aspect’s context menu and select Properties.
b.
Check the Default aspect check box under the Aspect Details tab.
c.
Click Apply.
16. Double-click the faceplate aspect to view the result as shown below.
For additional information on configuration of faceplates please read the instruction
Industrial
IT
Base System, Engineering - Graphics.
Adding Alarm and Event Handling
The Alarm and Event Configuration aspect on the signal objects are used to create
events and alarms based on the properties received from the PLC.
The events and alarms are viewed and accessed by the operator using alarm and
event lists. A top level alarm list, which is handling all alarms in the installation,
is preconfigured. It is possible to configure other alarm lists on lower levels, for
example for a section of the site or a single motor. See the section about alarms in
the Industrial
IT
Base System, Operator Workplace Configuration instruction for
more details.
To create an event or alarm the signal has to be configured, this is done in the Alarm
and Event Configuration aspect on an object type or on the individual signal
instance.
Object instances that generates events and alarms are recommended to be placed in
the Functional Structure to be able to have alarm lists that covers only parts of the
plant. The chapter Building the Functional Structure shows how to create an
appropriate functional structure.
Содержание IndustrialIT Compact HMI 800
Страница 1: ...IndustrialIT Compact HMI 800 System Version 4 1 Getting Started ...
Страница 2: ......
Страница 3: ...IndustrialIT Compact HMI 800 System Version 4 1 Getting Started ...
Страница 18: ...Terminology About This Book 18 3BSE040587R4401 ...
Страница 20: ...System Overview Section 1 Compact HMI 800 Overview 20 3BSE040587R4401 ...
Страница 46: ...IP Addresses and Workgroups Section 3 Installation 46 3BSE040587R4401 ...
Страница 88: ...Import to Compact HMI 800 Section 4 Engineering 88 3BSE040587R4401 ...
Страница 111: ...Section 5 Operation Alarm and Event Usage 3BSE040587R4401 111 Figure 70 System Event List ...
Страница 112: ...Alarm and Event Usage Section 5 Operation 112 3BSE040587R4401 ...
Страница 188: ...Creating New Graphical Libraries Section 8 PLC Connect Graphic Elements 188 3BSE040587R4401 ...
Страница 191: ......