Startup Operation
34 - EN
ProcessMaster / HygienicMaster
CI/FEP300/FEH300-EN
Instructions on using the Qmax menu (flow range end value)
The device is factory calibrated to the flow range end value Qmax
DN
, unless other customer
information is available. The ideal flow range end values are approximately 2-3 m/s
(0.2 ... 0.3 x Q
max
DN). The smallest and largest possible flow range end values are shown in the
table in the chapter "Flowmeter sizes. flow range".
Information regarding factory settings for further parameters (unless customer has
requested a specific parametrization)
• Current
output
The factory setting for the current output is 4 ... 20 mA (active).
•
Digital output DO1 (terminals 51/52)
Digital output DO1 is preconfigured as a passive pulse output (factory default).
• Empty
pipe
detection
Empty pipe detection is deactivated (factory default).
4.3.3 Changing to the information level
Press the
◄
key to change to the information
level of the process display.
Use the
▲
+
▼
keys to select the desired
information.
The Diagnostics menu contains the help text or
troubleshooting instructions.
If several operator pages are preconfigured via
the "Display" menu, you can switch manually
here to the respective operator page.
If the "Multiplex" function is switch on in the
"Display" menu, you can automatically switch to
the next operator page via "Autoscroll".
The "Signal View" menu is described in detail, for
service purposes, in a separate service manual.