6.2.8.4. I1004 Operating Mode LOCAL/GLOBAL/REMOTE
Dip Switch I1004
Function
1 2 3 4 5
ON
X
OFF
LOCAL/GLOBAL
ON
OFF
X
LOCAL/REMOTE
Table 11
Dip Switch I1004-5
6.2.8.5. I1004 Behaviour under Energy failure conditions (capacitor voltage)
Dip Switch I1004
Function
1 2 3 4 5
ON
X
OFF
Energy failure autotrip, active
ON
OFF
X
Energy failure autotrip, inactive
Table 12
Dip Switch I1004-1
6.2.9. Jumper
The position of the jumpers should only be read after disconnecting the power supply with a complete discharge
of capacitors. Setting the jumper position is only possible with the power supply disconnected and capacitors
completely discharged.
Danger! Important!
6.2.9.1. JP1001 –Standard Open / Protection Trip
Setting of BI Y4 to “Standard Open“ or “Protection trip“ input
Jumper JP1001
Function
1 2 3
Input active as protection trip
Input active as standard open
Table 13
Jumper 1001
6.2.9.2. JP1019 – EnergY CONSUMPTION
By setting this jumper, the power consumption is reduced during the capacitor charging time. As a result, the
charging time is extended accordingly.
Jumper JP1019
Function
OFF
Standard energy consumption
~75W
ON
Reduced energy consumption
~33W
Table 14
Jumper 1019
Example of Jumper Position 2-3