34/36
selector switch (if fitted)
Only for Version APPL.0
: No operation possible
by the remote control
Check the Dip Switch I1004-5 configuration
and the position of the LOCAL/REMOTE or
GLOBAL selector switch (if fitted)
Energy in the capacitors is too low for a CO
operation
Restore auxiliary voltage.
See points “
Ready
LED flashing“
No remote control is possible
Check all external connections
An O operation is not
executed
Actuator opening coil is defective
Check actuator opening coil
Capacitors are not connected
Check the connection plug and capacitor cable
Remote signals for opening are not given
Check the connections of the signal cable
Setting of Jumper JP1001 with function and
input BI Y4 are not correct
Check the correct Jumper setting. With a
PR5xy device, JP1001 must be in position 1+2.
Undervoltage monitoring is not activated
Correct setting of the undervoltage threshold
and delay with dip switch I1001 and I1004
Push button panel is not connected correctly or
is defective
Check plug or exchange component
Apparatus closes and
opens automatically
Position sensor for ON position is not connected
correctly or is defective
Check connector and check operation with a
metal ruler (change of LED indicators)
Apparatus does not go to the final ON position
Check whether foreign bodies obstruct
movement.
Status check of the drive mechanism
Capacitors are defective
Check the voltage (80V) and change
components if necessary
Apparatus opens if the
auxiliary voltage supply is
disconnected
Undervoltage monitoring is activated and the
undervoltage signal input is connected with the
same power supply
Connect undervoltage signal input with a
different power supply
Capacitor energy failure function is activated
If possible, deactivate function with dip-switch
I1004
All output signals are open The voltage of the capacitors is less than
46VDC
Restore auxiliary voltage
Same behaviour immediately after disconnecting
the auxiliary voltage supply. Ready LED goes
out at the same time.
Check the connection plug and capacitor
cables
Apparatus has been
switched off by signal at
Y3
Signal input Y3 is configured as “Safe OFF“ and
CPU is defective
Contact ABB
The “Auto-Reclose”
function is not executed.
Apparatus only opens
Signal input Y6 “Lock in open“ is not active
Close signal input and repeat procedure
ON signal is not active (signal inputs or ON
button of the push button panel)
To obtain a “re-close” after a normal ON
switching action, the ON signal must be
cancelled and reactivated.
The “Auto-Reclose”
function is only executed
once
Faulty ON signal sequence (signal inputs or ON
button of the push button panel)
After every “Reclose” function, the ON signal
must be cancelled. For a series of repeat
functions, the ON signal must be cancelled and
reactivated
No correct startup of the
apparatus or unusual
Ready LED indicated
Check whether jumpers other than those
described in the operating manual are set
Remove those jumpers not described and
perform restart after complete discharge of the
capacitors
No change in function after
jumper or dip-switch
changes
Auxiliary voltage supply was not disconnected or
capacitors still have voltage
Disconnect auxiliary voltage supply and
discharge capacitors completely. After a
restart, the new setting is activated.