11/36
Fig. 10 Manual opening mechanism
3.1.7. Manual opening from pole level
To get access to the manual tripping catch, the threaded plug has to be removed. This can be done by means of
a coin or screwdriver. After removing the plug, the manual tripping crank can be introduced into the hole in the
front cover plate and the apparatus can be tripped by counter clockwise rotation of the hand crank
.
Fig. 11 Manual opening mechanism
3.1.8. Electrical pole interlocking (option)
With this functionality which is mounted on the control box, the operation of the pole can be blocked either in the
“open” or “closed” position. If the lever is in the “service” position, normal operation is activated. If the lever is in
the “interlocked” position, no “remote” or “local” opening or closing operation will be executed. Both lever
positions can be locked by one or multiple padlocks
.
Fig. 12 Electrical pole interlocking system
3.2. Identification
3.2.1. Apparatus
Содержание FSK II S +