Commissioning
58
FV4000-VT4/VR4 / FS4000-ST4/SR4
D184B097U02
6.6
Checking the parameters
ABB Automation Products sets the parameters of the measuring system and assigns all
necessary values on the basis of the ordering information. Since the devices are suitable for
universal use (i. e., for fluids and gases), we recommend checking and if necessary modifying
the following parameters in the transmitter during installation and start-up.
Parameter
Check
Nominal size
• Check value on name plate.
k factor
• The value displayed must match the value on the flowmeter
sensor.
Operating mode
• Select the required operating mode.
• Which flow unit is the meter to display the flow in/is the flowmeter
to add values?
• Selection between units of volume and units of mass flow
(depending upon the selected operating mode).
• Enter the required measuring range in the unit selected above with
the "Qmax operating mode" parameter.
• Range 0.15 ... 1.15 x "QmaxDN operation"
Qmin operation
• Check the low flow value.
• Range 0.05 ... 0.1 x QmaxDN
Unit totalizer
• Select the unit of flow for internal flow totalizing with the parameter.
This unit is also valid for the pulse output (switching output via
terminals 41 / 42).
Damping
• The response time of the electronics affects the local display, the
pulse output and the transducer block.
Display submenu
• Configuration of the local display
• Configuration of the switching output, if applicable
Содержание FS4000-SR4
Страница 1: ...Operating Instruction D184B097U02 Vortex Flowmeter Swirl Flowmeter FV4000 VT4 VR4 FS4000 ST4 SR4 ...
Страница 125: ...Appendix D184B097U02 FV4000 VT4 VR4 FS4000 ST4 SR4 125 ...
Страница 126: ...Appendix 126 FV4000 VT4 VR4 FS4000 ST4 SR4 D184B097U02 ...
Страница 127: ...Appendix D184B097U02 FV4000 VT4 VR4 FS4000 ST4 SR4 127 ...
Страница 128: ...Appendix 128 FV4000 VT4 VR4 FS4000 ST4 SR4 D184B097U02 ...
Страница 129: ...Appendix D184B097U02 FV4000 VT4 VR4 FS4000 ST4 SR4 129 ...
Страница 135: ......