Mounting
D184B097U02
FV4000-VT4/VR4 / FS4000-ST4/SR4
29
4.4
Installation at high media temperatures > 150°C (302 F)
At high media temperatures > 150°C (302 F) the flowmeter sensor must be installed so that the
transmitter is pointing to the side or downward (see the figure below).
G00616
Fig. 15: Installation at high media temperatures > 150°C (302°F)
4.5
Installation for pressure and temperature measurement
As an option, the flowmeter can be fitted with a PT100 for direct temperature measurement.
This temperature measurement supports, for example, the monitoring of the media temperature
or the direct measurement of saturated steam in mass flow units.
If pressure and temperature are to be compensated externally (e. g. with the "Sensycal"), the
measuring points must be installed as illustrated in the figure below.
G00617
15 x D
3 ... 5 D 2 ... 3 D
T
P
Fig. 16: Arrangement of temperature and pressure measuring points