Note:
The failure rate of the PTC sensor is not included in the
calculations.
1. FPTC drive STO, two-channel configuration. See
.
2. FPTC drive STO + FSO module with STO function
request, two-channel configuration. See
3. FPTC drive STO + external safety relay, two-channel
configuration. See
.
4. FPTC drive STO, one-channel configuration. See
.
5. FPTC drive STO + FSO module with STO function
request, one-channel configuration. See
One-channel
configurations
Two-channel configurations
5
4
3
2
1
Configuration
1
1
2
2
2
SIL / SILCL
c
c
c
c
c
PL
>60
>60
>90
>90
>90
SFF (%)
8.25E-09
7.68E-09
5.48E-09
5.54E-09
5.48E-09
PFH (1/h)
T
1
= 20 a
6.71E-05
6.17E-05
4.81E-05
4.88E-05
4.81E-05
PFD
avg
T
1
= 2 a
1.69E-04
1.56E-04
1.20E-04
1.21E-04
1.20E-04
PFD
avg
T
1
= 5 a
0
0
60
60
60
DC (%)
2
2
2
2
2
SC
1
1
1
1
1
Cat.
0
0
0
0
0
HFT
65
65
65
65
65
CCF
20
20
20
20
20
T
M
(a)
3AXD10000454332 E
The MTTF
D
value (EN ISO 13849-1) of the FPTC-02 module:
•
1708 years (two-channel connection)
•
1703 years (one-channel connection)
Technical data 83
Содержание FPTC-02
Страница 2: ......
Страница 4: ......
Страница 23: ... Layout 1 1 2 4 3 XSTO2 XSTO1 XWRN XFLT Retaining clips 1 Lock 2 Hardware description 23 ...
Страница 28: ...28 ...
Страница 37: ...2 3 1 4 Mechanical installation 37 ...
Страница 38: ...38 ...
Страница 48: ...48 ...
Страница 64: ...64 ...
Страница 70: ...70 ...
Страница 78: ...78 ...
Страница 89: ...Technical data 89 ...
Страница 90: ...90 Technical data ...
Страница 92: ...92 Technical data ...
Страница 93: ...Check the latest version of the certificate in the ABB Library Technical data 93 ...