![ABB FPTC-02 Скачать руководство пользователя страница 57](http://html.mh-extra.com/html/abb/fptc-02/fptc-02_user-manual_2723057.webp)
Description
Example
value
Name
Index
Sets the digital input that is connected
to the secondary input of the STO
function.
DI X113:4
& X114:4
STO input B
STO.12
Note:
In a non-redundant system, you
can use a one-channel input (for ex-
ample,
DI X113:4
).
Sets the time after which the drive can
restart when the FSO module has activ-
ated the STO function and opened the
drive STO circuit. With this parameter,
you can let the drive restart before the
motor has stopped (fly-start). This
parameter is applicable only if the STO
function is requested from STO input
A (
) or STO input B (
).
2000 ms
Restart delay
after STO
STO.13
STO function: Adjust the value when
necessary. If you do not want to use
the fly-start feature, set this parameter
to the same value as parameter
Parameter settings 57
Содержание FPTC-02
Страница 2: ......
Страница 4: ......
Страница 23: ... Layout 1 1 2 4 3 XSTO2 XSTO1 XWRN XFLT Retaining clips 1 Lock 2 Hardware description 23 ...
Страница 28: ...28 ...
Страница 37: ...2 3 1 4 Mechanical installation 37 ...
Страница 38: ...38 ...
Страница 48: ...48 ...
Страница 64: ...64 ...
Страница 70: ...70 ...
Страница 78: ...78 ...
Страница 89: ...Technical data 89 ...
Страница 90: ...90 Technical data ...
Страница 92: ...92 Technical data ...
Страница 93: ...Check the latest version of the certificate in the ABB Library Technical data 93 ...