Action
Restart the drive and the motor. Make sure that they operate normally.
If in use, test the XWRN input: Connect a resistor (resistance
100 ohm … 1 kohm) between the XWRN inputs. Make sure that the
motor temperature warning indication is activated in motor overtemper-
ature and short-circuit situations.
Fill in and sign the acceptance test report which verifies that the safety
function is safe and accepted to operation.
Start-up and acceptance test 69