42 Start-up
The start sequence for the parameter example above is given
below.
Control word:
•
Reset the fieldbus communication fault (if active).
•
Enter 7Eh (126 decimal)
→
SWITCH-ON DISABLED.
•
Enter 7Fh (127 decimal)
→
OPERATION ENABLED.
1001 EXT1
COMMANDS
10
= COMM
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 1.
1102 EXT1/EXT2 SEL
0
= EXT1
Enables external control location
1/2 selection through the fieldbus.
1103 REF1 SELECT
8
= COMM
Selects the fieldbus reference 1
as the source of the speed
reference.
1601 RUN ENABLE
7
= COMM
Selects the fieldbus interface as
the source for the inverted Run
enable signal (Run disable).
1604 FAULT RESET
SEL
8
= COMM
Selects the fieldbus interface as
the source for the fault reset
signal.
1) Read-only or automatically detected/set
2) Example
Drive parameter
Setting for ACS355
drives
Description
Содержание FEPL-02 Ethernet POWERLINK
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 20: ...20 About the manual ...
Страница 28: ...28 Mechanical installation ...
Страница 63: ...Start up 63 2 To add the adapter module right click the IF3 list entry and then click Insert ...
Страница 69: ...Start up 69 3 In the Project transfer dialog box click OK 4 Wait for the transfer to finish ...
Страница 70: ...70 Start up When the transfer is finished the PLC starts up in the RUN mode ...
Страница 90: ...90 Communication profiles ...
Страница 100: ...100 Communication protocol ...
Страница 104: ...104 Diagnostics ...
Страница 108: ...108 Technical data ...
Страница 140: ...140 Appendix C IdentResponse Frame ...