40 Start-up
Starting up ACS355 drives
1. Power up the drive.
2. Enable the communication between the adapter module and
the drive with parameter
9802 COMM PROT SEL
.
3. Set the FEPL configuration parameters in group
51
.
•
Select the communication profile with parameter
5102
.
•
Configure the network settings with parameters
5103
and
5104
.
4. With parameter
3018 COMM FAULT FUNC
, select how the
drive reacts to a fieldbus communication break.
5. With parameter
3019 COMM FAULT TIME
, define the time
between communication break detection and the selected
action.
6. Validate the settings made in parameter group
51
with
parameter
5127 FBA PAR REFRESH
.
7. Set the relevant drive control parameters to control the drive
according to the application. Examples of appropriate values
are shown in the tables below.