Select the value you want from the list
and confirm pressing the
↵
key (enter).
Press ESC twice
Before accessing the Main Menu, the following box will appear:
Accept the new configuration
Reject the new configuration (the previous configuration is retained)
Change the previously input values.
To select the required option use the
↓
(arrow down),
↑
(arrow up) keys, and press
↵
(enter) to confirm.
13.4.3.1
Modification of basic configuration
No parameter settings
can be made if the PR122/P unit is in alarm conditions.
The configuration of the unit must be done in EDIT mode.
Following the instructions given in par. 13.4.3, view the following on the display:
Change system date
Change system time
Select system language
1/4
t=0.14b/(i
-1)
0.02
T=13.5b/(i-1)
t=k/i
2
Function
1/3
Confirm
Abort
Modify
Confirm
Programming
1/4
January 12, 2003
Time
Language
Date
System
4/4
****
Language
New Password
Time
System
Password
Enter password
0***
To change the system password, select the relevant menu item and press
↵
(enter); then you will be prompted to enter the OLD password, and
afterwards you can input the new one twice.
Press ESC twice to return to the Main Menu
Before accessing the Main Menu, the following box will appear:
Accept the new configuration
Reject the new configuration (the previous configuration is retained)
Change the previously input values.
To select the required option, use the
↓
(arrow down),
↑
(arrow up) keys, and press
↵
(enter) to confirm.
1/3
Confirm
Abort
Modify
Confirm
Programming
Note: To set the system language check that:
-
the relay is set to local (when PR120/D-M is installed);
-
the CB is open;
-
auxiliary power supply is connected (Vaux 24VDC and/or busbar voltage through PR120/V and/or PR030/B).
If one of the above conditions is not met, the relay does not allow the language to be changed.