II F 3-12
Table 3.7/4:
Main Status Word
Table 3.7/5:
Auxiliary Status Word
Auxiliary Status Word (8.02)
ABB Drive Profile Control Word
Bit
Name
Function
0
LOGG_DATA_READY
1
OUT_OF_WINDOW
2
EMERG_STOP_CO-
AST
3
reserved
(reserved)
4
ON_DISABLED
External interlocking
OFF1_N (Digital input
selected by 15.14)
prevents the run
5
SYNC_RDY
Position counter
synchronous ready status
6
FEX1_ACK
FEX 1 acknowledge
7
FEX2_ACK
FEX 2 acknowledge
8
reserved
(reserved)
9
LIMITING
see signals 8.03, 8.04
10
TORQ_CONTROL
Drive is torque controlled
11
ZERO_SPEED
Motor speed actual is zero
12
EMF-SPEED
EMF speed feedback
selected
13
FAULT_OR_ALARM
Fault or alarm of drive
14
DRIVE_DIR_ASW
Negative drive direction
active
15
AUTO_RECLOSING
auto reclosing logic
activated
Table 3.7/6:
DI Status Word
Main Status Word (8.01)
ABB Drive Profile Control Word
Bit
Name
Function
0
RDY_ON
ready to close the contactor
1
RDY_RUN
ready to generate torque
2
RDY_REF
torque control operating
(running)
3
TRIPPED
indication of fault in DC
Device
4
OFF_2_STA_N
1: No OFF2 active
5
OFF_3_STA_N
1: No OFF3 active
6
ON_INHIBITED
Switch on inhibited
7
ALARM
indication of alarm in DC
Device
8
AT_SETPOINT
Setpoint/act.value monitoring
in the tolerance
9
REMOTE
1:Remote control / 0:Local
control
10
ABOVE_LIMIT
speed treshold value (50.10)
reached
11
reserved
(reserved)
12
reserved
(reserved)
13
reserved
(reserved)
14
reserved
(reserved)
15
reserved
(reserved)
DI Status Word (8.05)
Digital input status word of DCS 600 MultiDrive
Bit
Name
Function
0
DI 1
configurable
1
DI 2
configurable
2
DI 3
configurable
3
DI 4
configurable
4
DI 5
configurable
5
DI 6
configurable
6
DI 7
configurable
7
DI 8
configurable
8
DI 9
programmable Drive, if SDCS-IOE-1 is present
9
DI 10
programmable Drive, if SDCS-IOE-1 is present
10
DI 11
programmable Drive, if SDCS-IOE-1 is present
11
DI 12
programmable Drive, if SDCS-IOE-1 is present
12
DI 13
programmable Drive, if SDCS-IOE-1 is present
13
DI 14
programmable Drive, if SDCS-IOE-1 is present
14
DI 15
programmable Drive, if SDCS-IOE-1 is present
15
IOE1
1: SDCS-IOE-1 is connected to SDCS-CON-1
configurable: The DI can be selected for several converter functions; inversion function is available; in addition, it may be used for
application running.
available for programmable Drive: The DI is not selectable for converter functions, but is available for application programming.