GAA610-M
ADVANCED EMISSION GAS MONITORING SYSTEM | OI/GAA610-M-EN REV. B
69
Analyzer cabinet air conditioner problems
Problem
Cause
Remedy
Unit won’t cool
• Clogged fins on coil(s)
• Dirty filter
• Clean fins and filter, see
Cleaning and changing the inlet air filter
on
page 83.
• Blowers not running
• Compressor not running
• Compressor runs, but has bad valves
• Loss of refrigerant
• Check air conditioner.
Compressor tries to start but won’t run
• Low line voltage at start.
Should be ±10 % of rated voltage.
• Compressor motor stuck
• Bad contactor
• Bad overload switch
• Bad run/start capacitor
• Check air conditioner.
Unit blows breakers
• Undersized breaker/fuse or not time
delayed
• Short in system
• Check air conditioner.
Getting water in enclosure
• Drain plugged
• Drain tube kinked
• Check condensate drain.
• Enclosure not sealed (allowing humidity
in)
• Mounting gasket damaged
• Check gasket between air conditioner and analyzer cabinet.