Parameters 189
If enabled by parameter
, selects the
source for the activation of jogging function 2. (Jogging
function 2 can also be activated through fieldbus
regardless of parameter
.)
1 = Jogging 2 active.
For the selections, see parameter
.
Note:
If both jogging 1 and 2 are activated, the one that
was activated first has priority.
Enable signals
warning function
Selects enable signal (for example, run enable, start
enable) warnings to be suppressed. This parameter can
be used to prevent these warnings from flooding the event
log.
Whenever a bit of this parameter is set to 1, the
corresponding warning is suppressed, that is no warning is
generated even if the signal is switched off.
The bits of this binary number correspond to the following
warnings:
00b
00b…11b
Suppression of “enable signal missing” warnings.
1 = 1
21
Start and stop modes; emergency stop mode and signal
source selection; DC magnetization settings; autophasing
mode selection.
Selects the motor start function for the DTC motor control
mode, ie. when
is set to
.
Notes:
• The start function for the scalar motor control mode is
.
• Starting into a rotating motor is not possible when DC
magnetizing is selected (
or
).
• With permanent magnet motors and synchronous
reluctance motors,
start mode must be used.
• This parameter cannot be changed while the drive is
running.
See also section
(page
).
Fast
The drive pre-magnetizes the motor before start. The pre-
magnetizing time is determined automatically, being
typically 200 ms to 2 s depending on motor size. This
mode should be selected if a high break-away torque is
required.
0
No.
Name/Value
Description
Def/
FbEq16
Bit
Name
Warning
0
Enable Start
1
Run enable 1
2…15
Reserved
Содержание ACS880 ESP
Страница 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Страница 4: ......
Страница 28: ...28 PCP ESP control start up ...
Страница 30: ...30 Using the control panel ...
Страница 94: ...94 Standard programposi features ...
Страница 100: ...100 Default control connections ...
Страница 360: ...360 Parameters ...
Страница 362: ...362 Additional parameter data Fieldbus addresses Refer to the User s Manual of the fieldbus adapter ...
Страница 436: ...436 Fault tracing ...
Страница 486: ...486 Control chain diagrams ...
Страница 492: ...492 Appendix ESP with step up transformer and sine filter ...
Страница 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...