Parameters 211
Defines a speed reference correction, ie. a value added to
the existing reference between ramping and limitation.
This is useful to trim the speed if necessary, for example to
adjust draw between sections of a paper machine.
Note: For safety reasons, the correction is not applied
when an emergency stop is active.
WARNING! If the speed reference correction
exceeds
, a ramp stop may
be impossible. Make sure the correction is reduced
or removed when a ramp stop is required.
See the control chain diagram on page
.
0.00 rpm
-10000.00
…10000.00 rpm
Speed reference correction.
See par.
Defines the time constant of the speed error low-pass filter.
If the used speed reference changes rapidly, the possible
interferences in the speed measurement can be filtered
with the speed error filter. Reducing the ripple with this
filter may cause speed controller tuning problems. A long
filter time constant and fast acceleration time contradict
one another. A very long filter time results in unstable
control.
0 ms
0…10000 ms
Speed error filtering time constant. 0 = filtering disabled.
1 = 1 ms
No.
Name/Value
Description
Def/
FbEq16
Содержание ACS880 ESP
Страница 1: ...ABB industrial drives Firmware manual ACS880 PCP ESP control program ...
Страница 4: ......
Страница 28: ...28 PCP ESP control start up ...
Страница 30: ...30 Using the control panel ...
Страница 94: ...94 Standard programposi features ...
Страница 100: ...100 Default control connections ...
Страница 360: ...360 Parameters ...
Страница 362: ...362 Additional parameter data Fieldbus addresses Refer to the User s Manual of the fieldbus adapter ...
Страница 436: ...436 Fault tracing ...
Страница 486: ...486 Control chain diagrams ...
Страница 492: ...492 Appendix ESP with step up transformer and sine filter ...
Страница 494: ...Contact us www abb com drives www abb com drivespartners 3AXD50000016186 Rev B EN 2015 10 27 ...