Standard programposi features 93
du/dt filter support
With an external du/dt filter connected to the output of the drive, bit 13 of
must be switched on. The setting enables an overtemperature
protection for the filter. Note that the setting is not to be activated with inverter
modules with internal du/dt filters.
Settings
(page
Sine filter support
The control program has a setting that enables the use of ABB sine filters (available
separately). With a sine filter connected to the output of the drive, bit 1 of
must be switched on. The setting forces the drive to use the
scalar motor control mode, and limits the switching and output frequencies to
• prevent the drive from operating at filter resonance frequencies, and
• protect the filter from overheating.
Please contact your local ABB representative before connecting a sine filter from
another manufacturer.