Guidelines for planning the electrical installation 71
Implementing the ATEX-certified Safe motor
disconnection function (Q971)
With Q971, the drive provides ATEX-certified safe motor disconnection without
contactor using the drive Safe torque off function. For more information, see
ACS880
ATEX-certified Safe disconnection function application guide
(3AUA0000132231 [English])
or
FPTC-02 ATEX-certified thermistor protection module, Ex II (2) GD (option
+L537+Q971) for ACS880 drives user’s manual
(3AXD50000027782 [English]).
Implementing safety functions provided by the FSO
safety functions module (oQ972 and +Q973)
The drive can be equipped with an FSO-xx safety functions module (Q972 or
+Q973) which enables the implementation of functions such as Safe brake control (SBC),
Safe stop 1 (SS1), Safe stop emergency (SSE), Safely limited speed (SLS) and Safe
maximum speed (SMS).
The settings of the FSO module are at default when delivered from the factory. The wiring
of the safety circuit and configuration of the FSO module are the responsibility of the
machine builder.
The FSO module reserves the standard Safe torque off (STO) connection of the drive
control unit. STO can still be utilized by other safety circuits through the FSO.
For wiring instructions, safety data and more information on the functions provided by the
options, see
FSO-12 safety functions module user’s manual
(3AXD50000015612
[English]) or
FSO-21 safety functions module user’s manual
(3AXD50000015614
[English]).
Declaration of Conformity
EU Declaration of Conformity (Machinery Directive)
page
.
Implementing the Power loss ride-through function
Implement the power loss ride-through function as follows:
1. Check that the power-loss ride-through function of the drive is enabled with parameter
30.31 Undervoltage control
in the ACS880 primary control program.
2. If the installation is equipped with a main contactor, prevent its tripping at the input
power break. For example, use a time delay relay (hold) in the contactor control circuit.
WARNING!
Make sure that the flying restart of the motor will not cause any
danger. If you are in doubt, do not implement the power-loss ride-through
function.
Содержание ACS880-34
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 34 drive modules 132 to 400 kW 200 to 450 hp Hardware manual ...
Страница 4: ......
Страница 14: ...14 ...
Страница 22: ...22 Safety instructions ...
Страница 28: ...28 Introduction to the manual ...
Страница 42: ...42 Operation principle and hardware description ...
Страница 118: ...118 External control unit ...
Страница 140: ...140 Installation example with full cabling panels option H381 M8 16 Hex 2 5 4 3 1 1 1 1 2 6 7 ...
Страница 152: ...152 Installation checklist ...
Страница 156: ...156 Start up ...
Страница 158: ...158 Fault tracing ...
Страница 174: ...174 Maintenance ...
Страница 202: ...202 Technical data EU Declaration of Conformity Machinery Directive ...
Страница 204: ...204 Technical data ...
Страница 206: ...206 Dimension drawings Standard configuration 3AXD50000038012 ...
Страница 207: ...Dimension drawings 207 Location of power cable connection terminals with options H370 H356 3AXD50000038012 ...
Страница 208: ...208 Dimension drawings Drive module with options 0B051 H356 0H371 3AXD50000038012 ...
Страница 209: ...Dimension drawings 209 Configuration with option H381 3AXD50000323210 ...
Страница 210: ...210 Dimension drawings LCL filter module 3AXD50000206162 ...
Страница 214: ...214 Dimension drawings External control unit 3axd50000011687 ...
Страница 238: ...238 Resistor braking ...
Страница 242: ...242 du dt and sine filters ...
Страница 256: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035191 Rev B EN 2018 09 28 ...