![ABB ACS880-34 Скачать руководство пользователя страница 194](http://html.mh-extra.com/html/abb/acs880-34/acs880-34_hardware-manual_2653194.webp)
194 Technical data
Network type
TN (grounded) and IT (ungrounded) systems
Short-circuit withstand
strength (IEC 61439-1)
Maximum allowable prospective short-circuit current is 65 kA when by the
fuses given in the fuse table. For the maximum allowable prospective short-
circuit current with circuit breakers, see section
Protecting the drive and input
on page
.
Short-circuit current protection
(UL 61800-5-1)
The drive is suitable for use on a circuit capable of delivering not more than
100,000 rms symmetrical amperes at 600 V maximum when protected by
fuses given in the fuse table.
Short-circuit current protection
(CSA C22.2 No. 14-05)
The drive is suitable for use on a circuit capable of delivering not more than
100 kA rms symmetrical amperes at 600 V maximum when by the fuses
given in the fuse table.
Frequency (
f
1
)
50/60 Hz, Variation ± 5% of nominal frequency.
Imbalance
Max.
± 3% of nominal phase to phase input voltage
Power factor
cos phi
1
= 1, cos phi (total) = 0.99
Harmonic distortion
Harmonics are below the limits defined in IEEE519, IEC61000-3-12 and G5/4
standards.
The table below shows typical results on indicated networks. Values are
measured at the input terminals of the drive.
Motor connection data
Motor types
Asynchronous AC induction motors, permanent magnet motors, AC induction
servomotors and ABB synchronous reluctance motors (SynRM motors)
Voltage (
U
2
)
0 to
U
1
,
3-phase symmetrical. This is indicated in the type designation label
as typical output voltage level as 3
0…
U
1
,
U
max
at the field weakening
point.
Frequency (
f
2
)
0…500 Hz
Note
: Operation above 150 Hz can require type-specific derating. For more
information, contact your local ABB representative.
For drives with du/dt filter: 120 Hz
For drives with sine filter: 120 Hz
Frequency resolution
0.01 Hz
Current
See section
Frequency (
f
2
)
0…500 Hz
For drives with du/dt filter: Contact ABB
For drives with sine filter: Contact ABB
Switching frequency
3 kHz (typically)
Maximum recommended
motor cable length
DTC control
Scalar control
500 m (1640 ft)
500 m (1640 ft)
THD =
I
n
I
1contmax
50
2
2
R
sc
THD voltage (%)
THD current (%)
20
3
2.5*
100
01.9
2.5*
THD
Total harmonic distortion. The voltage THD depends on the short-
circuit ratio (Rsc). The spectrum of the distortion also contains
interharmonics.
I
n
nth harmonic component
R
sc
Short-circuit ratio.
R
sce
=
I
sc
/
I
N
I
sc
Short-circuit current at point of common coupling (PCC)
I
1contmax
Continuous maximum input current of the line-side converter
I
L
Maximum demand load current
~
Содержание ACS880-34
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 34 drive modules 132 to 400 kW 200 to 450 hp Hardware manual ...
Страница 4: ......
Страница 14: ...14 ...
Страница 22: ...22 Safety instructions ...
Страница 28: ...28 Introduction to the manual ...
Страница 42: ...42 Operation principle and hardware description ...
Страница 118: ...118 External control unit ...
Страница 140: ...140 Installation example with full cabling panels option H381 M8 16 Hex 2 5 4 3 1 1 1 1 2 6 7 ...
Страница 152: ...152 Installation checklist ...
Страница 156: ...156 Start up ...
Страница 158: ...158 Fault tracing ...
Страница 174: ...174 Maintenance ...
Страница 202: ...202 Technical data EU Declaration of Conformity Machinery Directive ...
Страница 204: ...204 Technical data ...
Страница 206: ...206 Dimension drawings Standard configuration 3AXD50000038012 ...
Страница 207: ...Dimension drawings 207 Location of power cable connection terminals with options H370 H356 3AXD50000038012 ...
Страница 208: ...208 Dimension drawings Drive module with options 0B051 H356 0H371 3AXD50000038012 ...
Страница 209: ...Dimension drawings 209 Configuration with option H381 3AXD50000323210 ...
Страница 210: ...210 Dimension drawings LCL filter module 3AXD50000206162 ...
Страница 214: ...214 Dimension drawings External control unit 3axd50000011687 ...
Страница 238: ...238 Resistor braking ...
Страница 242: ...242 du dt and sine filters ...
Страница 256: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035191 Rev B EN 2018 09 28 ...