![ABB ACS880-34 Скачать руководство пользователя страница 58](http://html.mh-extra.com/html/abb/acs880-34/acs880-34_hardware-manual_2653058.webp)
58 Guidelines for planning the electrical installation
Selecting the supply disconnecting device
Install a hand-operated input disconnecting device between the AC power source and the
drive. The disconnecting device must be of a type that can be locked to the open position
for installation and maintenance work.
European Union
To agree with the European Union Directives, according to standard EN 60204-1,
Safety
of Machinery
, the disconnecting device must be one of the following types:
•
switch-disconnector of utilization category AC-23B (EN 60947-3)
•
disconnector that has an auxiliary contact that in all cases causes switching devices to
break the load circuit before the opening of the main contacts of the disconnector
(EN 60947-3)
•
circuit breaker suitable for isolation in accordance with EN 60947-2.
Other regions
The disconnecting device must conform to the applicable safety regulations.
Selecting the main contactor
If a main contactor is used, its utilization category (number of operations under load) must
be AC-1 according to IEC 60947-4,
Low-voltage switchgear and controlgear
. Select the
contactor according to the nominal voltage and current of the drive.
Examining the compatibility of the motor and drive
Use an asynchronous AC induction motor, permanent magnet motor, AC induction
servomotor or ABB synchronous reluctance motor (SynRM motor) with the drive. Several
induction motors can be connected at a time.
Select the motor size and drive type from the rating tables in chapter
on
basis of the AC line voltage and motor load. Use the DriveSize PC tool if you need to tune
the selection more in detail.
Make sure that the motor withstands the maximum peak voltage in the motor terminals,
see the
on page
. For basics of protecting the motor insulation and
bearings in drive systems, refer to section
Protecting the motor insulation and bearings
below.
Note:
•
Consult the motor manufacturer before you use a motor which nominal voltage differs
from the AC line voltage connected to the drive input.
•
The voltage peaks at the motor terminals are relative to the supply voltage of the drive,
not the drive output voltage.
•
If the motor and drive are not of the same size, consider the following operation limits
of the drive control program:
•
motor nominal voltage range 1/6 ... 2 ·
U
N
•
motor nominal current range 1/6 ... 2 ·
I
N
of the drive in DTC control and 0 ... 2 ·
I
N
in scalar control. The control mode is selected by a drive parameter.
Содержание ACS880-34
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 34 drive modules 132 to 400 kW 200 to 450 hp Hardware manual ...
Страница 4: ......
Страница 14: ...14 ...
Страница 22: ...22 Safety instructions ...
Страница 28: ...28 Introduction to the manual ...
Страница 42: ...42 Operation principle and hardware description ...
Страница 118: ...118 External control unit ...
Страница 140: ...140 Installation example with full cabling panels option H381 M8 16 Hex 2 5 4 3 1 1 1 1 2 6 7 ...
Страница 152: ...152 Installation checklist ...
Страница 156: ...156 Start up ...
Страница 158: ...158 Fault tracing ...
Страница 174: ...174 Maintenance ...
Страница 202: ...202 Technical data EU Declaration of Conformity Machinery Directive ...
Страница 204: ...204 Technical data ...
Страница 206: ...206 Dimension drawings Standard configuration 3AXD50000038012 ...
Страница 207: ...Dimension drawings 207 Location of power cable connection terminals with options H370 H356 3AXD50000038012 ...
Страница 208: ...208 Dimension drawings Drive module with options 0B051 H356 0H371 3AXD50000038012 ...
Страница 209: ...Dimension drawings 209 Configuration with option H381 3AXD50000323210 ...
Страница 210: ...210 Dimension drawings LCL filter module 3AXD50000206162 ...
Страница 214: ...214 Dimension drawings External control unit 3axd50000011687 ...
Страница 238: ...238 Resistor braking ...
Страница 242: ...242 du dt and sine filters ...
Страница 256: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035191 Rev B EN 2018 09 28 ...