![ABB ACS880-34 Скачать руководство пользователя страница 129](http://html.mh-extra.com/html/abb/acs880-34/acs880-34_hardware-manual_2653129.webp)
Internal control unit (P905) 129
Analog outputs AO1 and
AO2
(XAO)
Connector pitch 5 mm (0.2 in), wire size 2.5 mm
2
(14 AWG)
0…20 mA,
R
load
< 500 ohm
Frequency range: 0…300 Hz
Resolution: 11 bit + sign bit
Inaccuracy: 2% of full scale range
Drive-to-drive link
(XD2D)
Connector pitch 5 mm, wire size 2.5 mm
2
Physical layer: RS-485
Maximum cable length of the link: 50 m
Cable type: Shielded twisted pair cable with twisted pair for data and a wire
or pair for signal ground, nominal impedance 100…165 ohm, for example
Belden 9842
Transmission rate: 8 Mbit/s
Termination by jumper
Embedded Modbus RTU
XD2D
Connector pitch 5 mm, wire size 2.5 mm
2
Physical layer: RS-485
Cable type: Shielded twisted pair cable with twisted pair for data and a wire
or pair for signal ground, nominal impedance 100…165 ohm, for example
Belden 9842
Transmission rate: 9.6…115.2 kbit/s
Termination by switch
Safe torque off connection
(XSTO)
Connector pitch 5 mm (0.2 in), wire size 2.5 mm
2
(14 AWG)
Input voltage range: -3…30 V DC
Logic levels: “0” < 5 V, “1” > 17 V
For the drive to start, both connections must be closed (OUT1 to IN1 and
IN2).
Current consumption 50 mA (+24 V DC, continuous) per STO channel
Maximum output current from OUT1 (24 V DC continuous): 100 mA
EMC (immunity) according to IEC 61326-3-1
Control panel / PC
connection
Connector: RJ-45
Cable length < 3 m (10 ft)
The terminals of the control unit fulfill the Protective Extra Low Voltage (PELV) requirements. The PELV
requirements of a relay output are not fulfilled if a voltage higher than 48 V is connected to the relay output.
Содержание ACS880-34
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 34 drive modules 132 to 400 kW 200 to 450 hp Hardware manual ...
Страница 4: ......
Страница 14: ...14 ...
Страница 22: ...22 Safety instructions ...
Страница 28: ...28 Introduction to the manual ...
Страница 42: ...42 Operation principle and hardware description ...
Страница 118: ...118 External control unit ...
Страница 140: ...140 Installation example with full cabling panels option H381 M8 16 Hex 2 5 4 3 1 1 1 1 2 6 7 ...
Страница 152: ...152 Installation checklist ...
Страница 156: ...156 Start up ...
Страница 158: ...158 Fault tracing ...
Страница 174: ...174 Maintenance ...
Страница 202: ...202 Technical data EU Declaration of Conformity Machinery Directive ...
Страница 204: ...204 Technical data ...
Страница 206: ...206 Dimension drawings Standard configuration 3AXD50000038012 ...
Страница 207: ...Dimension drawings 207 Location of power cable connection terminals with options H370 H356 3AXD50000038012 ...
Страница 208: ...208 Dimension drawings Drive module with options 0B051 H356 0H371 3AXD50000038012 ...
Страница 209: ...Dimension drawings 209 Configuration with option H381 3AXD50000323210 ...
Страница 210: ...210 Dimension drawings LCL filter module 3AXD50000206162 ...
Страница 214: ...214 Dimension drawings External control unit 3axd50000011687 ...
Страница 238: ...238 Resistor braking ...
Страница 242: ...242 du dt and sine filters ...
Страница 256: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035191 Rev B EN 2018 09 28 ...