62 Guidelines for planning the electrical installation
Additional data for calculating the rise time and the peak line-to-line voltage
The diagrams below show the relative peak line-to-line voltage and rate of change of
voltage as a function of the motor cable length with and without a d
u
/d
t
filter in use.
To calculate the actual peak voltage for a certain cable length read the relative
Û
LL
/
U
N
value from the appropriate diagram and multiply it by the nominal supply voltage (
U
N
).
To calculate the actual voltage rise time for a certain cable length read the relative values
Û
LL
/
U
N
and (d
u
/d
t
)/U
N
from the appropriate diagram. Multiply the values by the nominal
supply voltage (U
N
) and substitute into equation
t
= 0.8 ·
Û
LL
/(d
u
/d
t
).
Additional note for sine filters
Sine filters protect the motor insulation system. Therefore, the d
u
/d
t
filter can be replaced
with a sine filter. The peak phase-to-phase voltage with the sine filter is approximately
1.5 ·
U
N
.
Additional note for common mode filters
Common mode filters are available as plus code E208.
600 V <
U
N
< 690 V
Reinforced:
Û
LL
= 1800 V
+ N + d
u
/d
t
+ CMF
Reinforced:
Û
LL
= 2000 V,
0.3 microsecond rise time
***
N + CMF
***If the intermediate DC circuit voltage of the drive is increased from the nominal level by resistor braking,
check with the motor manufacturer if additional output filters are needed in the applied drive operation
range.
Drive with d
u
/d
t
filter
Drive without d
u
/d
t
filter
I
Motor cable length
Û
LL
/
U
N
Relative peak line-to-line voltage
d
u
/d
t
/U
N
Relative d
u
/d
t
value
Note
: ÛLL and du/dt values are approximately 20% higher with resistor braking.
Nominal AC supply
voltage
Requirement for
Motor insulation system
ABB d
u
/d
t
filter, insulated N-end bearing and ABB
common mode filter
100
200
300
0.0
0.5
1.0
1.5
2.0
2.5
3.0
l
(m)
du/dt
UN
-------------(1/
s)
Û
LL
/
U
N
Û
LL
/
U
N
l
(m)
du/dt
UN
-------------(1/
s)
1.0
2.0
5.0
4.0
3.0
1.5
2.5
3.5
4.5
100
200
300
5.5
Содержание ACS880-34
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 34 drive modules 132 to 400 kW 200 to 450 hp Hardware manual ...
Страница 4: ......
Страница 14: ...14 ...
Страница 22: ...22 Safety instructions ...
Страница 28: ...28 Introduction to the manual ...
Страница 42: ...42 Operation principle and hardware description ...
Страница 118: ...118 External control unit ...
Страница 140: ...140 Installation example with full cabling panels option H381 M8 16 Hex 2 5 4 3 1 1 1 1 2 6 7 ...
Страница 152: ...152 Installation checklist ...
Страница 156: ...156 Start up ...
Страница 158: ...158 Fault tracing ...
Страница 174: ...174 Maintenance ...
Страница 202: ...202 Technical data EU Declaration of Conformity Machinery Directive ...
Страница 204: ...204 Technical data ...
Страница 206: ...206 Dimension drawings Standard configuration 3AXD50000038012 ...
Страница 207: ...Dimension drawings 207 Location of power cable connection terminals with options H370 H356 3AXD50000038012 ...
Страница 208: ...208 Dimension drawings Drive module with options 0B051 H356 0H371 3AXD50000038012 ...
Страница 209: ...Dimension drawings 209 Configuration with option H381 3AXD50000323210 ...
Страница 210: ...210 Dimension drawings LCL filter module 3AXD50000206162 ...
Страница 214: ...214 Dimension drawings External control unit 3axd50000011687 ...
Страница 238: ...238 Resistor braking ...
Страница 242: ...242 du dt and sine filters ...
Страница 256: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035191 Rev B EN 2018 09 28 ...