Technical data
91
Input power connection
Voltage (
U
1
)
208/220/230/240 VAC 3-phase
± 10 % for 230 VAC units
380/400/415 VAC 3-phase
± 10 % for 400 VAC units
380/400/415/440/460/480/500 VAC 3-phase
± 10 % for 500 VAC units
The output voltage can be raised with setting of parameter 23.01 DC VOLT REF. Example:
With 400 V supply voltage and 700 VDC intermediate DC circuit voltage, it is possible to
run a 500 V motor at the motor nominal voltage.
Prospective short-circuit
current (IEC 60439-1,
UL 508C)
Maximum allowed prospective short-circuit current in the supply is 65 kA in a second
providing that the mains cable of the drive is protected with appropriate fuses.
US and Canada: The drive is suitable for use on a circuit capable of delivering not more
than 65 kA rms symmetrical amperes at the drive nominal voltage when protected by T
class fuses.
Frequency
48 to 63 Hz, maximum rate of change 17 %/s
Imbalance
Max.
± 3 % of nominal phase to phase input voltage
Voltage dips
Max. 25 %
Fundamental power factor
(cos phi
1
)
1.00 (fundamental at nominal load)
Harmonic distortion
THD current < 0.05 ·
I
1cont.max
if supply network voltage is not distorted by other loads
Motor connection
Voltage (
U
2
)
0 to
U
1
,
3-phase symmetrical,
U
max
at the field weakening point
Frequency
DTC mode: 0 to 3.2 ·
f
FWP
. Maximum frequency 300 Hz.
f
FWP
=
f
FWP
: frequency at field weakening point;
U
Nmains
: mains (input power) voltage;
U
Nmotor
: rated motor voltage;
f
Nmotor
: rated motor frequency
Frequency resolution
0.01 Hz
Current
See section
Power limit
Approximately 1.3 ·
P
cont.max
Field weakening point
8 to 300 Hz
Switching frequency
3 kHz (average).
Maximum recommended
motor cable length
300 m (984 ft). Additional restriction for units with EMC filtering (type code selections
+E202 and +E200): max. motor cable length is 100 m (328 ft). With longer cables the EMC
Directive requirements may not be fulfilled.
Efficiency
Approximately 97 % at nominal power level
~
400 VAC
700 VDC
~
M
3 ~
500 VAC
U
Nmains
U
Nmotor
·
f
Nmotor
Содержание ACS800-11
Страница 1: ...ACS800 Hardware Manual ACS800 11 Drives 5 5 to 110 kW ACS800 U11 Drives 7 5 to 125 HP ...
Страница 4: ......
Страница 12: ...Safety instructions 12 ...
Страница 30: ...The ACS800 11 U11 30 ...
Страница 36: ...Mechanical installation 36 ...
Страница 54: ...Planning the electrical installation 54 ...
Страница 59: ...Electrical installation 59 1 2 3 Views of frame size R5 U1 V1 W1 V2 W2 U2 UDC UDC 5 5 PE 6 6 8 9 9 ...
Страница 74: ...Installation checklist 74 ...
Страница 84: ...Operation 84 ...
Страница 104: ...Technical data 102 ...
Страница 105: ...Dimensional drawings 103 Dimensional drawings The dimensions are given in millimetres and inches ...
Страница 108: ...Dimensional drawings 106 ...
Страница 111: ...External 24 V power supply for the RMIO board 109 5 6 7 8 ...
Страница 112: ...External 24 V power supply for the RMIO board 110 ...
Страница 113: ......