Operation
81
Connection diagram of the RMIO board in the line-side converter
Internal connections to the RMIO board for the ACS800 IGBT Supply Control
Program are shown below. Do not change the connections.
X20
1
VREF-
Reference voltage -10 VDC,
1 kohm <
R
L
< 10 kohm
2
GND
X21
1
VREF+
Reference voltage 10 VDC,
1 kohm <
R
L
< 10 kohm
2
GND
3
AI1+
By default, not in use. 0(2) ... 10 V,
R
in
> 200 kohm
4
AI1-
5
AI2+
By default, not in use. 0(4) ... 20 mA
,
R
in
= 100 ohm
6
AI2-
7
AI3+
By default, not in use. 0(4) ... 20 mA
,
R
in
= 100 ohm
8
AI3-
9
AO1+
By default, not in use. 0(4)...20 mA,
R
in
= 100 ohm
10
AO1-
11
AO2+
By default, not in use. 0(4)...20 mA,
R
in
= 100 ohm
12
AO2-
X22
1
DI1
Acknowledgement of converter fan
1)
2
DI2
Stop/Start
3
DI3
Acknowledgement from main contactor
1)
4
DI4
By default not in use.
5
DI5
By default not in use.
6
DI6
Reset
1)
7
+24V
+24 VDC max. 100 mA
8
+24V
9
DGND
Digital ground
10
DGND
Digital ground
11
DI7(DIIL) By default not in use.
X23
1
+24V
Auxiliary voltage output, non-isolated,
24 VDC 250 mA
2
GND
X25
1
RO11
Relay output 1: Charging contactor
control
1)
2
RO12
3
RO13
X26
1
RO21
Relay output 2: fault (-1)
2
RO22
3
RO23
X27
1
RO31
Relay output 3: Main contactor
control
1)
2
RO32
3
RO33
1)
non-programmable I/O
K1
Содержание ACS800-11
Страница 1: ...ACS800 Hardware Manual ACS800 11 Drives 5 5 to 110 kW ACS800 U11 Drives 7 5 to 125 HP ...
Страница 4: ......
Страница 12: ...Safety instructions 12 ...
Страница 30: ...The ACS800 11 U11 30 ...
Страница 36: ...Mechanical installation 36 ...
Страница 54: ...Planning the electrical installation 54 ...
Страница 59: ...Electrical installation 59 1 2 3 Views of frame size R5 U1 V1 W1 V2 W2 U2 UDC UDC 5 5 PE 6 6 8 9 9 ...
Страница 74: ...Installation checklist 74 ...
Страница 84: ...Operation 84 ...
Страница 104: ...Technical data 102 ...
Страница 105: ...Dimensional drawings 103 Dimensional drawings The dimensions are given in millimetres and inches ...
Страница 108: ...Dimensional drawings 106 ...
Страница 111: ...External 24 V power supply for the RMIO board 109 5 6 7 8 ...
Страница 112: ...External 24 V power supply for the RMIO board 110 ...
Страница 113: ......