Notes
Wiring method
Free air
Prefer symmetrical shielded VFD cable.
Enclosures, air handlers, etc.
Allowed internally in enclosures when in ac-
cordance with UL.
1) Metallic conduit may be used as an additional ground path, provided this path is a solid path capable
of handling ground currents.
2) See NFPA NFPA 70 (NEC), UL, and local codes for your application.
3) Non-metallic conduit use underground is allowed; however, these installations inherently have an
increased chance for nuisance problems due to the potential for water/moisture in the conduit.
Water/moisture in the conduit increases the likelihood of VFD faults or warnings. Proper installation
is required to make sure there is no intrusion of water/moisture.
Metal conduit
Couple separate parts of a metal conduit together: bridge the joints with a ground
conductor bonded to the conduit on each side of the joint. Also bond the conduits
to the drive enclosure and motor frame. Use separate conduits for input power,
motor, brake resistor, and control wiring. Do not run motor wiring from more than
one drive in the same conduit.
■
Power cable shield
If the cable shield is used as the sole protective earth (PE) conductor, make sure
that its conductivity agrees with the PE conductor requirements.
To effectively suppress radiated and conducted radio-frequency emissions, the
cable shield conductivity must be at least 1/10 of the phase conductor conductivity.
The requirements are easily met with a copper or aluminum shield. The minimum
requirement of the motor cable shield of the drive is shown below. It consists of
a concentric layer of copper wires with an open helix of copper tape or copper
wire. The better and tighter the shield, the lower the emission level and bearing
currents.
110 Guidelines for planning the electrical installation
Содержание ACS580 Series
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS580 01 drives Hardware manual...
Страница 2: ......
Страница 4: ......
Страница 19: ...Further information Table of contents 19...
Страница 20: ...20...
Страница 34: ...34...
Страница 58: ...58...
Страница 128: ...128...
Страница 163: ...R5 4 6 11 11 10 4 3 5 7 8 9 0 5 0 6 N m 0 4 lbf ft 8 4 Electrical installation Global IEC 163...
Страница 206: ...R5 DC DC L1 L2 L3 T1 U T2 W T2 V 11 11 7 3 9 5 10 6 4 R5 0 4 lbf ft 206 Electrical installation North America...
Страница 207: ...R6 R9 11 11 7 3 9 5 10 6 4 R6 R9 0 4 lbf ft Electrical installation North America 207...
Страница 214: ...214...
Страница 227: ...Note Only 24 V DC can be used for STO Only PNP input configuration can be used Control unit 227...
Страница 236: ...236...
Страница 240: ...240...
Страница 242: ...242...
Страница 258: ...3a 3b 3c 4 5 7 6 2d 2a 2b 2c 258 Maintenance...
Страница 364: ...Frame R1 IP21 UL Type 1 3AXD10000601652 364 Dimension drawings...
Страница 365: ...Frame R1 IP55 UL Type 12 3AXD10000601699 Dimension drawings 365...
Страница 366: ...Frame R1 IP55 F278 UL Type 12 366 Dimension drawings...
Страница 367: ...Frame R1 IP66 UL Type 4X B066 3AXD50001012694 Dimension drawings 367...
Страница 368: ...Frame R1 IP66 UL Type 4X B063 3AXD50001012694 368 Dimension drawings...
Страница 369: ...Frame R1 IP66 UL Type 4X C193 3AXD50001012694 Dimension drawings 369...
Страница 370: ...Frame R2 IP21 UL Type 1 3AXD10000602398 370 Dimension drawings...
Страница 371: ...Frame R2 IP55 UL Type 12 3AXD10000602401 Dimension drawings 371...
Страница 372: ...Frame R2 IP55 F278 UL Type 12 372 Dimension drawings...
Страница 373: ...Frame R2 IP66 UL Type 4X B066 3AXD50000999286 Dimension drawings 373...
Страница 374: ...Frame R2 IP66 UL Type 4X B063 3AXD50000999286 374 Dimension drawings...
Страница 375: ...Frame R2 IP66 UL Type 4X C193 3AXD50000999286 Dimension drawings 375...
Страница 376: ...Frame R3 IP21 UL Type 1 3AXD10000602466 376 Dimension drawings...
Страница 377: ...Frame R3 IP55 UL Type 12 3AXD10000602519 Dimension drawings 377...
Страница 378: ...Frame R3 IP55 E223 UL Type 12 378 Dimension drawings...
Страница 379: ...Frame R3 IP55 F278 F316 UL Type 12 Dimension drawings 379...
Страница 380: ...Frame R3 IP66 UL Type 4X B066 3AXD50001013059 380 Dimension drawings...
Страница 381: ...Frame R3 IP66 UL Type 4X B063 3AXD50001013059 Dimension drawings 381...
Страница 382: ...Frame R3 IP66 UL Type 4X C193 3AXD50001013059 382 Dimension drawings...
Страница 383: ...Frame R4 IP21 UL Type 1 3AXD10001330082 Dimension drawings 383...
Страница 384: ...Frame R4 IP55 UL Type 12 3AXD10001330271 384 Dimension drawings...
Страница 385: ...Frame R4 IP55 E223 UL Type 12 3AXD10001373680 Dimension drawings 385...
Страница 386: ...Frame R4 IP55 F278 F316 UL Type 12 3AXD10001373680 386 Dimension drawings...
Страница 387: ...Frame R5 IP21 UL Type 1 3AXD10000427933 Dimension drawings 387...
Страница 388: ...Frame R5 IP55 UL Type 12 3AXD10000386017 388 Dimension drawings...
Страница 389: ...Frame R5 IP55 E223 UL Type 12 Dimension drawings 389...
Страница 390: ...Frame R5 IP55 F278 F316 UL Type 12 390 Dimension drawings...
Страница 391: ...Frame R6 IP21 UL Type 1 3AXD10000258705 Dimension drawings 391...
Страница 392: ...Frame R6 IP55 UL Type 12 3AXD10000330667 392 Dimension drawings...
Страница 393: ...Frame R7 IP21 UL Type 1 3AXD10000258995 Dimension drawings 393...
Страница 394: ...Frame R7 IP55 UL Type 12 3AXD10000330932 394 Dimension drawings...
Страница 395: ...Frame R8 IP21 UL Type 1 3AXD10000287670 Dimension drawings 395...
Страница 396: ...Frame R8 IP55 UL Type 12 3AXD10000332446 396 Dimension drawings...
Страница 397: ...Frame R9 IP21 UL Type 1 3AXD10000287428 Dimension drawings 397...
Страница 398: ...Frame R9 IP55 UL Type 12 3AXD10000334310 398 Dimension drawings...
Страница 437: ...Dimension drawings The dimensions are in millimeters Optional I O extension and adapter modules 437...
Страница 459: ...Optional I O extension and adapter modules 459...
Страница 460: ...460...