![ABB ACS580 Series Скачать руководство пользователя страница 23](http://html2.mh-extra.com/html/abb/acs580-series/acs580-series_hardware-manual_5041639023.webp)
•
Before you adjust the drive operation limits, make sure that the motor and all
driven equipment can operate throughout the set operation limits.
•
Before you activate the automatic fault reset or automatic restart functions
of the drive control program, make sure that no dangerous situations can
occur. These functions reset the drive automatically and continue operation
after a fault or supply break. If these functions are activated, the installation
must be clearly marked as defined in IEC/EN/UL 61800-5-1, subclause 6.5.3,
for example, "THIS MACHINE STARTS AUTOMATICALLY".
•
The maximum number of drive power-ups is five in ten minutes. Too frequent
power-ups can damage the charging circuit of the DC capacitors.
•
If you have connected safety circuits to the drive (for example, Safe torque off
or emergency stop), validate them at start-up. See separate instructions for
the safety circuits.
•
Beware of hot air exiting from the air outlets.
•
Do not cover the air inlet or outlet when the drive is running.
Note:
•
If you select an external source for the start command and it is on, the drive
will start immediately after fault reset unless you configure the drive for pulse
start. See the firmware manual.
•
If the drive is in remote control mode, you cannot stop or start the drive with
the control panel.
•
Only authorized persons are allowed to repair a malfunctioning drive.
Safety instructions 23
Содержание ACS580 Series
Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS580 01 drives Hardware manual...
Страница 2: ......
Страница 4: ......
Страница 19: ...Further information Table of contents 19...
Страница 20: ...20...
Страница 34: ...34...
Страница 58: ...58...
Страница 128: ...128...
Страница 163: ...R5 4 6 11 11 10 4 3 5 7 8 9 0 5 0 6 N m 0 4 lbf ft 8 4 Electrical installation Global IEC 163...
Страница 206: ...R5 DC DC L1 L2 L3 T1 U T2 W T2 V 11 11 7 3 9 5 10 6 4 R5 0 4 lbf ft 206 Electrical installation North America...
Страница 207: ...R6 R9 11 11 7 3 9 5 10 6 4 R6 R9 0 4 lbf ft Electrical installation North America 207...
Страница 214: ...214...
Страница 227: ...Note Only 24 V DC can be used for STO Only PNP input configuration can be used Control unit 227...
Страница 236: ...236...
Страница 240: ...240...
Страница 242: ...242...
Страница 258: ...3a 3b 3c 4 5 7 6 2d 2a 2b 2c 258 Maintenance...
Страница 364: ...Frame R1 IP21 UL Type 1 3AXD10000601652 364 Dimension drawings...
Страница 365: ...Frame R1 IP55 UL Type 12 3AXD10000601699 Dimension drawings 365...
Страница 366: ...Frame R1 IP55 F278 UL Type 12 366 Dimension drawings...
Страница 367: ...Frame R1 IP66 UL Type 4X B066 3AXD50001012694 Dimension drawings 367...
Страница 368: ...Frame R1 IP66 UL Type 4X B063 3AXD50001012694 368 Dimension drawings...
Страница 369: ...Frame R1 IP66 UL Type 4X C193 3AXD50001012694 Dimension drawings 369...
Страница 370: ...Frame R2 IP21 UL Type 1 3AXD10000602398 370 Dimension drawings...
Страница 371: ...Frame R2 IP55 UL Type 12 3AXD10000602401 Dimension drawings 371...
Страница 372: ...Frame R2 IP55 F278 UL Type 12 372 Dimension drawings...
Страница 373: ...Frame R2 IP66 UL Type 4X B066 3AXD50000999286 Dimension drawings 373...
Страница 374: ...Frame R2 IP66 UL Type 4X B063 3AXD50000999286 374 Dimension drawings...
Страница 375: ...Frame R2 IP66 UL Type 4X C193 3AXD50000999286 Dimension drawings 375...
Страница 376: ...Frame R3 IP21 UL Type 1 3AXD10000602466 376 Dimension drawings...
Страница 377: ...Frame R3 IP55 UL Type 12 3AXD10000602519 Dimension drawings 377...
Страница 378: ...Frame R3 IP55 E223 UL Type 12 378 Dimension drawings...
Страница 379: ...Frame R3 IP55 F278 F316 UL Type 12 Dimension drawings 379...
Страница 380: ...Frame R3 IP66 UL Type 4X B066 3AXD50001013059 380 Dimension drawings...
Страница 381: ...Frame R3 IP66 UL Type 4X B063 3AXD50001013059 Dimension drawings 381...
Страница 382: ...Frame R3 IP66 UL Type 4X C193 3AXD50001013059 382 Dimension drawings...
Страница 383: ...Frame R4 IP21 UL Type 1 3AXD10001330082 Dimension drawings 383...
Страница 384: ...Frame R4 IP55 UL Type 12 3AXD10001330271 384 Dimension drawings...
Страница 385: ...Frame R4 IP55 E223 UL Type 12 3AXD10001373680 Dimension drawings 385...
Страница 386: ...Frame R4 IP55 F278 F316 UL Type 12 3AXD10001373680 386 Dimension drawings...
Страница 387: ...Frame R5 IP21 UL Type 1 3AXD10000427933 Dimension drawings 387...
Страница 388: ...Frame R5 IP55 UL Type 12 3AXD10000386017 388 Dimension drawings...
Страница 389: ...Frame R5 IP55 E223 UL Type 12 Dimension drawings 389...
Страница 390: ...Frame R5 IP55 F278 F316 UL Type 12 390 Dimension drawings...
Страница 391: ...Frame R6 IP21 UL Type 1 3AXD10000258705 Dimension drawings 391...
Страница 392: ...Frame R6 IP55 UL Type 12 3AXD10000330667 392 Dimension drawings...
Страница 393: ...Frame R7 IP21 UL Type 1 3AXD10000258995 Dimension drawings 393...
Страница 394: ...Frame R7 IP55 UL Type 12 3AXD10000330932 394 Dimension drawings...
Страница 395: ...Frame R8 IP21 UL Type 1 3AXD10000287670 Dimension drawings 395...
Страница 396: ...Frame R8 IP55 UL Type 12 3AXD10000332446 396 Dimension drawings...
Страница 397: ...Frame R9 IP21 UL Type 1 3AXD10000287428 Dimension drawings 397...
Страница 398: ...Frame R9 IP55 UL Type 12 3AXD10000334310 398 Dimension drawings...
Страница 437: ...Dimension drawings The dimensions are in millimeters Optional I O extension and adapter modules 437...
Страница 459: ...Optional I O extension and adapter modules 459...
Страница 460: ...460...