MECHANICAL INSTALLATION
PRODUCT
ACS1000W
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS213400 E01
REV.
J
LANG.
en
PAGE
74/166
6.7. Installing the redundant fan
This section applies to drives that are equipped with the optional redundant fan.
1.
Remove the lifting rails (1 in Fig. 6
5).
2.
Fasten the two parts of the fan casing (3 and 4 in Fig. 6
5) to the roof and
with each other.
3.
Put the fan (5 in Fig. 6
5) into the casing and fasten it to the vibration
dampeners (6 in Fig. 6
5).
4.
Route the power supply cable through the rectangular opening (7 in Fig. 6
5)
into the cabinet and connect it inside the terminal box (8 in Fig. 6
5).
5.
Install the cover of the fan housing (9 in Fig. 6
5).
Figure 6
-
5 Installing the redundant fan
1) Lifting rails
2) Cover
3) Fan casing
4) Fan casing
5) Fan
6) Vibration dampeners
7) Opening
8) Terminal box
9) Fan housing
2
7
6
1
1
6
6
4
3
5
9
8