7.6.1.8. Preparing cables for cable entries with sealing modules
If the data sheet for the drive specifies the cable entry direction (ie, 'bottom';
'top'), the drive is delivered with the cable entry plates installed in the correct
locations; otherwise, the factory-installed cable entry plates must be moved to
their correct locations on-site.
–
Prepare cables with an outer cable screen or shield for EMC bonding with the
metal enclosure of the cabinet as illustrated in Fig. 7
Figure 7
-
14 Preparing power cables for sealing modules
–
Install the sealing modules according to the instructions of the sealing module
supplier.
1) Sealing module
2) Frame
3) Conductive foil of sealing module
4) Cable clamp
5) Shrinkable sheath seal
6) Heat-shrinkable termination
7) Outer cable sheath
8) Cable sheath removed to expose cable
shield
9) Shield extension to be connected to PG
busbar
10) Screen extension to be connected to the
PG busbar
11) Cable lug as specified by the cable supplier
and suitable for M12 bolt