ACS 300 User’s Manual
Chapter 8 - Fault Tracing
Note! If the fault persists, contact the nearest ACS 300 supplier.
THE DRIVE DOES NOT
FUNCTION
CORRECTLY IN
REMOTE CONTROL
CHECK:
•
the polarity of the signals
•
the position of switch S1
•
the position of jumper X5
CONTROL PANEL
Processor incompatible with
Control Panel.
•
Check the connection between
the processor and the panel.
Control card error
•
Contact your nearest ACS 300
supplier.
WRITE -> ACS ERROR
VERSION MISMATCH
Mismatch of ACS 300 software.
Note! Parameter copying
unsuccessful.
•
Set the parameters manually.
OUTPUT FREQUENCY
< REFERENCE
FREQUENCY
•
wrong parameter values
•
too much load
•
wrong motor connection
CHECK:
•
supply voltage (400 V series)
•
I LIMIT high enough
•
IR COMP not too high
•
motor connection Star/Delta
•
ACS 300 sizing with respect to
the load
Fault indication
Possible cause
Remedy