![ABB ACS 300 Скачать руководство пользователя страница 87](http://html.mh-extra.com/html/abb/acs-300/acs-300_user-manual_3269087.webp)
ACS 300 User’s Manual
73
Chapter 7 - Drive Parameters
Some points of view must be taken in consideration when this
parameter is active:
•
The Local Ref parameter is not displayed.
•
The texts on the control panel display for constant frequencies
will be CR1, CR2 and CR3. CR = Constant Reference. The
unit is %. With these parameters you can give constant
reference values in remote mode.
•
Joystick control does not operate. On the other hand PI
Control cannot be selected while Joystick control is active.
•
Custom settings have no effect.
•
The rotation direction cannot be changed.
•
Critical frequency ranges are ignored.
PI-ITIME
Defines the integral time of PI Controller. The setting range is 0.0
to 320.0 s. PI Controller operates as a P Controller when the
parameter value is 320.0 s.
PI-GAIN
Output frequency change
for a 10 % change in error
Output frequency change
for a 50 % change in error
50 %
0.75 Hz
3.75 Hz
100 %
1.5 Hz
7.5 Hz
300 %
4.5 Hz
22.5 Hz
Содержание ACS 300
Страница 14: ...xiv ACS 300 User s Manual Table of Contents ...
Страница 24: ...10 ACS 300 User s Manual Chapter 1 Overview of This Manual ...
Страница 28: ...14 ACS 300 User s Manual Chapter 2 Mechanical Installation ...
Страница 33: ...ACS 300 User s Manual 19 Chapter 3 Power Connections Figure 3 5 Cable connections for frame size R2 ...
Страница 50: ...36 ACS 300 User s Manual Chapter 4 Control Connections ...
Страница 60: ...46 ACS 300 User s Manual Chapter 6 Control and Parameter Logic ...