ACS 300 User’s Manual
29
Chapter 4 - Control Connections
Standard 2
Switch S1 is in the same position as in Standard selection.
Parameter PARAM SET has value 2.
Table 4-3 Standard 2 digital input functions.
Table 4-4 Standard 2 Constant speed selection
3-wire
3-wire is for general industrial applications which usually require
a three wire start/stop signal for safety reasons. With 3-wire
control, momentary start and stop push-buttons are used. The
start button is normally open, and the stop button is normally
closed. When operating from external momentary push-buttons,
the ACS 300 requires a start command to be given after power is
applied.
Digital input
Function
Notes
DI1
Start / Stop
C24 V DC to start
DI2
Reverse
C24 V DC to reverse
DI3
CS
Constant speed (=CS) selection,
refer to table 4-4
DI4
CS
DI5
Parameter set selection
0 V =set 1 and +24 V =set 2
DI3
DI4
DI5
Result
0
0
0
Speed reference from AI1
1
0
0
CS1 (parameter Page 2)
0
1
0
CS2 (parameter Page 2)
1
1
0
CS3 (parameter Page 2)
0
0
1
Speed reference from AI1
1
0
1
CS1 (parameter Page 4)
0
1
1
CS2 (parameter Page 4)
1
1
1
CS3 (parameter Page 4)
Содержание ACS 300
Страница 14: ...xiv ACS 300 User s Manual Table of Contents ...
Страница 24: ...10 ACS 300 User s Manual Chapter 1 Overview of This Manual ...
Страница 28: ...14 ACS 300 User s Manual Chapter 2 Mechanical Installation ...
Страница 33: ...ACS 300 User s Manual 19 Chapter 3 Power Connections Figure 3 5 Cable connections for frame size R2 ...
Страница 50: ...36 ACS 300 User s Manual Chapter 4 Control Connections ...
Страница 60: ...46 ACS 300 User s Manual Chapter 6 Control and Parameter Logic ...