68
ACS 300 User’s Manual
Chapter 7 - Drive Parameters
1 (Fault)
Relay is de-energised (and the Fault LED on the Control Panel
illuminates), when a fault occurs.
2 (Power)
Relay is energised all the time (after initialisation of the program).
Note! The relay is energised when this function is selected.
3 (I>Current Limit)
Relay is energised for a minimum of 250 ms whenever the output
current exceeds I LIMIT. The time is for hysteresis and slow
response of indication devices. Relay is de-energised when
current is reduced below I LIMIT.
4 (>Frequency limit)
Relay is de-energised when the output frequency exceeds the
value selected with parameter F SUPERV. Relay is energised
when output frequency is below (F SUPERV - hysteresis). If F
SUPERV is greater than 10 Hz the hysteresis is 2 Hz, otherwise
Code
Function
1
Fault
2
Power
3
I>Current limit
4
>Frequency limit
5
<Frequency limit
6
Motor is running forward
7
Motor is running
8
Motor overtemperature trip
9
Under panel control (LOCAL)
10
None
11
Fault (-1)
Содержание ACS 300
Страница 14: ...xiv ACS 300 User s Manual Table of Contents ...
Страница 24: ...10 ACS 300 User s Manual Chapter 1 Overview of This Manual ...
Страница 28: ...14 ACS 300 User s Manual Chapter 2 Mechanical Installation ...
Страница 33: ...ACS 300 User s Manual 19 Chapter 3 Power Connections Figure 3 5 Cable connections for frame size R2 ...
Страница 50: ...36 ACS 300 User s Manual Chapter 4 Control Connections ...
Страница 60: ...46 ACS 300 User s Manual Chapter 6 Control and Parameter Logic ...