32
ACS 300 User’s Manual
Chapter 4 - Control Connections
Alternate
Alternate mode has both Start forward and Start reverse inputs
(+24 V). The drive is stopped if both inputs are connected to 0 V
or +24 V. Parameter PARAM SET has value 1.
Table 4-9 Alternate digital input functions.
Figure 4-5 Alternate switch S1 selection.
Table 4-10 Start functions for Alternate.
Digital
input
Function
Notes
DI1
Start Forward
C24 V DC to Start Forward/Reverse
refer to Table 4-10.
DI2
Start Reverse
DI3
CS1
Constant speed (=CS) selection,
refer to Table 4-11.
DI4
CS2
DI5
ACC2/DEC2
0 V = ramp 1 and +24 V DC = ramp 2
DI1
DI2
Result
0
0
Drive stopped
+24 V
0
Run forward
0
+24 V
Run reverse
+24 V
+24 V
Drive stopped
OFF
ON
0
1
Alternate