06 MECHANICAL INSTALLATION
3BHS213401 E01 REV H
ACS1000 AIR-COOLED
USER MANUAL
78/184
6.4
Preparing the floor
Condition of the floor:
- Must support the weight of the cabinet
- Overall incline across 5 m must not exceed 5 mm
- Even
- Non-flammable, smooth and non- abrasive
- Protected against humidity diffusion
6.5
Fixing the cabinet to the floor
1. Drill fixing holes into the floor as indicated on the layout drawing.
2. When the cabinet is in place, check if the doors are misaligned.
Note:
If the doors do not open and close properly, place leveling plates at the appropriate
points (arrows in Fig. 6-1).
- Recommended size: 80 x 300 x 0.5 mm
Figure 6-1: Leveling the drive
3. Fix the cabinet to the floor.
Note:
Floor fixings are not supplied.
- Anchor bolts as illustrated, or screws and nuts of size M16 are recommended.
- Insert the screws from the ends of the cabinet base or via the holes inside the cabinet.
Important:
If the doors of medium voltage compartments cannot be opened,
contact the ABB service organization.
Содержание ACS 1013-A1
Страница 1: ... MEDIUM VOLTAGE AC DRIVES ACS1000 air cooled User manual ...
Страница 3: ...Contents ACS1000 air cooled User manual ...
Страница 5: ... 01 About this manual 01 3 14 ...
Страница 16: ......
Страница 17: ... 02 Important safety information 02 15 26 ...
Страница 28: ......
Страница 29: ... 03 Power electronics and cabinet features03 27 50 ...
Страница 53: ... 04 Control system 04 51 66 ...
Страница 68: ......
Страница 69: ... 05 Transportation storage and disposal05 67 74 ...
Страница 76: ......
Страница 77: ... 06 Mechanical installation 06 75 82 ...
Страница 84: ......
Страница 85: ... 07 Electrical installation07 83 106 ...
Страница 108: ......
Страница 109: ... 08 Commissioning 08 107 112 ...
Страница 115: ... 09 Operation 09 113 126 ...
Страница 129: ... 10 CDP control panel 10 127 150 ...
Страница 153: ... 11 Preventive and corrective maintenance 11 151 182 ...
Страница 185: ......