03 POWER ELECTRONICS AND CABINET FEATURES
3BHS213401 E01 REV H
ACS1000 AIR-COOLED
USER MANUAL
43/184
3.5.4
AC redundant fans - operating principles
Default settings:
- Cycle time during which AC fan 1 and AC fan 2 run alternately: 10 h
- Operating time of AC fan 1: 6 h
- Operating time of AC fan 2: 4 h
Figure 3-13: Operating times of the AC fan units during continuous drive operation (
A
) and
Intermittent drive operation (
B
)
When the drive operates continuously, AC fan 1 switches off after six hours and fan 2 switches
on for four hours.
When the drive operates intermittently, the AC fan that is due for operation is switched on and
off in the same pattern as the drive until the programmed operating time has elapsed.
If one AC fan fails, the second AC fan switches on and runs continuously.
(1) Cycle time
(2) Fan 1
(3) Fan 2
(4) 10 hours
(5) 6 hours
(6) 4 hours
(7) On
(8) Off
1
2
3
4
4
5
5
6
A
B
7
8
7
8
Содержание ACS 1013-A1
Страница 1: ... MEDIUM VOLTAGE AC DRIVES ACS1000 air cooled User manual ...
Страница 3: ...Contents ACS1000 air cooled User manual ...
Страница 5: ... 01 About this manual 01 3 14 ...
Страница 16: ......
Страница 17: ... 02 Important safety information 02 15 26 ...
Страница 28: ......
Страница 29: ... 03 Power electronics and cabinet features03 27 50 ...
Страница 53: ... 04 Control system 04 51 66 ...
Страница 68: ......
Страница 69: ... 05 Transportation storage and disposal05 67 74 ...
Страница 76: ......
Страница 77: ... 06 Mechanical installation 06 75 82 ...
Страница 84: ......
Страница 85: ... 07 Electrical installation07 83 106 ...
Страница 108: ......
Страница 109: ... 08 Commissioning 08 107 112 ...
Страница 115: ... 09 Operation 09 113 126 ...
Страница 129: ... 10 CDP control panel 10 127 150 ...
Страница 153: ... 11 Preventive and corrective maintenance 11 151 182 ...
Страница 185: ......