Different actions are taken depending on the severity of the fault. The IED tries to
eliminate the fault by restarting. After the fault is found to be permanent, the IED
stays in the internal fault mode. All other output contacts are released and locked
for the internal fault. The IED continues to perform internal tests during the fault
situation.
The internal fault code indicates the type of internal IED fault. When a fault appears,
the code must be recorded so that it can be reported to ABB customer service.
Fault indication
Fault code
Additional information
Internal Fault System error
2
An internal system error has
occurred.
Internal Fault File system er-
ror
7
A file system error has occur-
red.
Internal Fault Test
8
Internal fault test activated
manually by the user.
Internal Fault
SW watchdog error
10
Watchdog reset has occurred
too many times within an
hour.
Internal Fault License check
fail
117
The devices is equipped with
invalid license.
5.3.2
Warnings
Warnings are shown in the event list of the WHMI. The text Warning additionally
provided with the name of the warning, a numeric code as well as the date and time
is shown on the WHMI. The warning indication message can be manually cleared.
If a warning appears, record the name and code so that it can be
provided to ABB customer service.
Table 12: Warning indications and codes
Warning indication
Warning code
Additional information
Warning IEC61850 error
20
Error when building the IEC
61850 data model.
Warning Dataset error
24
Error in the Data set(s).
Warning
Report cont. error
25
Error in the Report control
block(s).
Warning
GOOSE contr. error
26
Error in the GOOSE control
block(s).
Warning
SCL config error
27
Error in the SCL configuration
file or the file is missing.
Warning Logic error
28
Too many connections in the
configuration.
Warning
SMT logic error
29
Error in the SMT connections.
Table continues on the next page
1MRS758850 D
Troubleshooting
SSC600
Operation Manual
61