IEC08000337.vsd
IEC08000337 V1 EN
Figure 77:
CMT: Container window design when selecting DNP3 protocol
Procedure to move signals:
1. Select one or several signals.
•
Click in the list of signals to select one signal.
•
Press
Shift
or
Ctrl
and several signals to select a set of signals.
•
Right-click in the list of signals, select
Select All
from the context menu
or press
Ctrl+A
to select all signals.
2. Press the blue arrow button to insert the selected signals into the configuration.
3. Press the green double arrow button to insert all signals into the configuration,
IEC08000361.vsd
IEC08000361 V1 EN
Figure 78:
CMT: Move buttons
4. Click the drop down list
Signal Type:
to select the other signal types for this
channel.
5. Repeat to move signals for all signal types and save the selection.
Content changes in the DNP3 container are marked with a star at
the end of the name, see
. The star indicates that changes
in the container have to be saved before leaving CMT.
Section 9
1MRK 511 261-UEN -
DNP3 communication engineering
108
650 series
Engineering Manual