— Operation related error messages
Error message Tx LCD message Possible cause
Suggested action
Tx response
M024.036
Power Supply
Warning
The Device Power Supply is close to the lowest
acceptable limit.
Check the Voltage at the terminal block and if it is
not within the valid range check the external
power supply.
no effect
M024.036
Power Supply
Warning
The Device Power Supply is close to the
highest acceptable limit.
Check the Voltage at the terminal block and if it is
not within the valid range check the external
power supply.
no effect
M022.041
Electronic
Temperature Out of
Limits
The Electronics temperature is out of its lower
acceptable limit . The circuitry for the
sampling of the Electronics Temperature has
failed.
The Electronics should be replaced as soon as
possible.
no effect
M022.041
Electronic
Temperature Out of
Limits
The Electronics temperature is out for its
Higher acceptable limit. The circuitry for the
sampling of the Electronics Temperature has
failed.
The Electronics should be replaced as soon as
possible.
no effect
— Process related error messages.
Error message Tx LCD message Possible cause
Suggested action
Tx response
F104.032
Pressure
Overrange
This effect could be produced by other equipment on
the process, (valves…..). Exceeding the pressure range
can cause reduced accuracy or mechanical damage to
the diaphragm material and may require calibration/
replacement.
The compatibility of pressure
transmitter model and process
conditions has to be checked. A
different transmitter type could be
required.
no effect
F102.004
P-dP Out Of
Limits
The measurement range has not been correctly
calculated OR an incorrect transducer model has been
selected.
The compatibility of pressure
transmitter model and process
conditions has to be checked. Probably
a different transmitter type is required.
no effect
F100.005
Static Pressure
Out of Limits
The static pressure of the process exceeds the limit of
the sensor. Exceeding the Static Pressure can reduce
accuracy, mechanically damage the diaphragm and may
require calibration/replacement. An incorrect transducer
model could have been selected.
The compatibility of pressure
transmitter model and process
conditions has to be checked. Probably
a different transmitter type is required.
no effect
S054.006
Sensor
Temperature Out
of Limits
The temperature of the process environment affects the
pressure transmitter; Excess temperature can reduce
accuracy, degrade device components and may require
calibration/replacement.
The compatibility of pressure
transmitter model and process
conditions has to be checked. A
different installation type could be
required e.g. use of remote seals.
no effect
S052.031
Max Working
Pressure Exceeded
The static pressure of the process exceeds the max
working Pressure supported by the transmitter.
Exceeding the Max Working Pressure can mechanically
damage the process connections (flanges, pipes….)
and/or be dangerous.
The compatibility of pressure
transmitter model and process
conditions has to be checked.
no effect
F098.034
Analog Output
Saturated
The analog output for the Primary Variable is beyond its
Low scaling limit and no longer represents the true
applied process. The Analog Output (4-20 mA) is
saturated to the configured Saturation Limit Low.
Adjust the Saturation Limit or the
working range if possible.
no effect
F098.034
Analog Output
Saturated
The analog output for the Primary Variable is beyond its
High scaling limit and no longer represents the true
applied process. The Analog Output (4-20 mA) is
saturated to the configured Saturation Limit High.
Adjust the Saturation Limit or the
working range if possible.
no effect
M018.038
PILD Output
One (HIGH or LOW) or both connections between the
pressure sensor and the process is blocked either by
plugging or closed valves.
Check valves and impulse line.
Clean impulse line if necessary and
initiate PILD training.
no effect
M016.039
PILD-Changed Op.
Conditions
Process conditions have changed to an extent that new
settings for the PILD algorithm are needed.
A new Training is necessary for this new
process condition.
no effect