2 6 6 H S H MODBUS TR A N S M IT TE R |
P R E SSU R E/ T EM P ER AT U R E M U LT I VA R I A B L E | O I/ 2 6 6 H SH M T- EN R E V. A
Communication
Exit
Select
Menu
9
Protocol Settings
Protocol
HART Address
Back
Select
1
Software
Back
1
Communication
Communication
Protocol Settings
Protocol Settings
Protocol
HART Address
Back
Select
1
Back
1
Communication
Operate/Modbus
Back
Select
1
Communication
Communication
Protocol
Protocol Settings
Protocol
HART Address
Back
Select
1
0
Back
Edit
1
Communication
Communication
HART Address
Min 0
Max 15
Next
OK
HART Address
Communication
- Protocol Settings
- Protocol
- HART Address
7.11 Damping (DAMPING)
Pressure transmitter output signals that are noisy as a
result of the process can be smoothed (damped)
electrically.
The additional time constant can be set between 0 s and
60 s in increments of 0.0001 s. Damping does not affect
the value shown on the digital display as a physical unit. It
only affects the parameters derived from this, such as the
analog output current, free process variable, input signal
for the controller, and so on.
The damping adjustment can be performed in different
ways:
— Via the the local HMI:
Enter the menu: > Device Setup > Output Scaling
> Damping.
Set the damping to the desired value.
— Via the Asset Vision Basic Software:
See Asset Vision Software Operating Instructions.
— Via the Hand Held Terminal:
See relevant operating instruction
7.13