81
Supply Fan
Factory Lubrication
Note:
Bearing lubrication only applies to
belt driven fan motors such as the energy
recovery wheel power exhaust fan motor.
All original fan motors and bearings are
furnished with factory lubrication. Some
applications will require that bearings be re-
lubricated periodically. The schedule will
depend on the operating duty, temperature
variations or other severe atmospheric
conditions.
Bearings should be re-lubricated when at
normal operating temperatures, but not
running. Rotate the fan shaft by hand and
add only enough grease to purge the seals.
DO NOT OVERLUBRICATE.
Recommended greases are:
SHELL OIL - DOLIUM R
CHEVRON OIL - SRI No. 2
TEXACO INC. - PREMIUM RB
Removal
Remove fan access panel on the back side of
the unit. Panel is attached with eight 5/16”
bolts.
Figure 32 - 2-6 ton Supply Fan
Remove wire connections from motor. For
EC motors unplug the wire harness at the
control module that connects to the unit
control panel.
Through the blower access opening, remove
the two 5/16” bolts that connect the blower
assembly to the inlet wall (see Figure 33).
Figure 33 - RQ Supply Fan Removal Bolts
Through the coil access door, remove the
two 5/16” bolts that connect the blower
assembly to the inlet wall from air entering
side of the wall (see Figure 33).
Slide blower assembly (wire frame motor
mount, motor, blower wheel, inlet, and
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
WARNING
Blower wheels and bands must be
inspected for excessive dust build up
periodically and cleaned if required.
Excessive dust build up on blower
wheels may cause an unbalanced
state; leading to vibration and/or
component failure. Damages due to
excessive dust build up will not be
covered under factory warranty.
CAUTION
Содержание RQ SERIES
Страница 2: ......
Страница 29: ...29 Figure 3 RQ Cabinet Standard and Power Exhaust Gasket Locations ...
Страница 43: ...43 Figure 21 Example 2 6 ton through the Base Gas Piping ...
Страница 49: ...49 Figure 22 Post Corner Hole Location Figure 23 Post Back Hole Location ...
Страница 50: ...50 Figure 24 Post Corner Hole Piping Figure 25 Post Back Hole Piping ...
Страница 67: ...67 Gas Heater Instructions Figure 27 Gas Heater Instructions ...
Страница 97: ......
Страница 98: ......
Страница 99: ......