2.
BelowLLT
- "Below Low Limit Time".
Range = 10sec-1800sec, and the default
is 10sec. If ‘LLTset’ temperature is not
reached within ‘BelowLLT’ after
reaching full output, the status relay will
operate.
3.
Stages
- Number of stages. Range = 1-6,
and the default is 1. The number of
stages can be determined using Table 15.
Table 15 - Stages of Electric Preheat
Tonnages
Feature 14B
Stages
RQ 2-6 tons
G = 10 kW
1
H = 15 kW
J = 20 kW
4.
LATset
- Leaving air temperature
setpoint. Range = 35°F-80°F, and the
default is 50°F.
5.
OATset
- Outside air temperature
setpoint. Range = 35°F-60°F, and the
default is 35°F.
6.
LLTset
-
“Low
Limit
Time”
temperature setpoint. Range = 35°F-
50°F, and the default is 35°F. If
‘LLTSet’ temperature is not reached
within ‘BelowLLT’ time after reaching
full output, the status relay will operate.
7.
RESETset
-
“Reset
Setpoint”
temperature. Range = 35°F-80°F, and
the default is 50°F.
8.
ManSTG -
Temporary manual override
a specified stage testing, 0=normal
operation, 1-6 to override corresponding
stages. Range = 0-6, and the default is 0.
The manual override may be used for
unit testing of each stage. Stage 1 will be
at 50% to test SCR and stages 2-6 will
be full capacity. A manual override will
expire in ten minutes if not manually
cancelled by resetting ‘ManSTG’ back
to zero.
Содержание RQ SERIES
Страница 2: ......
Страница 29: ...29 Figure 3 RQ Cabinet Standard and Power Exhaust Gasket Locations ...
Страница 43: ...43 Figure 21 Example 2 6 ton through the Base Gas Piping ...
Страница 49: ...49 Figure 22 Post Corner Hole Location Figure 23 Post Back Hole Location ...
Страница 50: ...50 Figure 24 Post Corner Hole Piping Figure 25 Post Back Hole Piping ...
Страница 67: ...67 Gas Heater Instructions Figure 27 Gas Heater Instructions ...
Страница 97: ......
Страница 98: ......
Страница 99: ......