Solution:  Investigate  for  malfunction  of  dust  disposal  device  –  rotary  valve,  screw 

conveyor. Consult relevant IOM  

 

Issue:    

Dust build up in hoppers 

Solution:  Failure to empty dust receptacle(s). Increase frequency of emptying. Consult 

maintenance log.  

 
Issue:    

Dust build up in hoppers 

Solution:  Air in-leakage at dust disposal device. See item 13.1 
 

Issue:    

Moisture in the collected material causes it to stick in the hopper. 

Solution:  Consider changing the process so that less moisture is drawn into the OptiFlo, 

or that some warm dry air  is included in the extraction system to drive the 

combined  flow  further  from  the  dew  point.  Consider  application  of  thermal 
insulation to the hopper walls and electrical trace heating 

 

 
 

14

 

 RECOMMENDED SPARE PARTS LIST 

 
 
 
 

 

Item 

 

Description 

Recommended On 

Hand Spares 



Internal Door Gasket 

External Door Gasket 

Diaphragm Valve Repair Kit 

Solenoid Valve Repair Kit 

REDClean Cartridge 

Pulse Controller 

Explosion Panel 

10% of doors 

10% of doors 

10% of set 

10% of set 

1 full set 

1  

Содержание OptiFlo RC Series

Страница 1: ...GDED IOM 215 A OptiFlo RC...

Страница 2: ...lean REDFiltration and Reliable Efficient Durable are registered trademarks of American Air Filter Company Inc d b a AAF International GDED IOM 215 A TO ORDER SPARE REPLACEMENT PARTS Call 1 800 477 12...

Страница 3: ...CT SHIPMENT 11 4 1 How the product ships 11 4 2 Items that ship separately 11 5 PRODUCT RECEIPT AT THE DESIGNATED DELIVERY POINT 11 5 1 Responsibilities of the customer or customer s agent 11 5 2 Rece...

Страница 4: ...PLOSION VENTS 20 10 1 Installation of the explosion vent 20 10 2 Assembly 20 10 3 Explosion Vent Burst Sensor 21 10 4 Servicing 22 10 5 Safety distance 22 11 START UP OPERATION 22 11 1 Start up checkl...

Страница 5: ...m very large multiple component assemblies which require significant and complex rigging handling and assembly on site to small compact assemblies that are easily handled and maneuvered In addition to...

Страница 6: ...l be allowed within the work perimeter 2 3 Dust explosions Dust explosions constitute a serious industrial hazard and may result in death serious injury and or devastating property damage It is the re...

Страница 7: ...The equipment shall be oriented so that the vent will discharge to an unoccupied zone Such a zone will be prohibited to personnel and shall not include critical equipment or services such as fuel sto...

Страница 8: ...nd moves in a true down flow direction between the filters The airstream passes through the media as the dust is collected on the filter media The clean air then moves through the tube sheet section a...

Страница 9: ...arranged three high 4RC modules have filters arranged four high and 5RC have filters arranged five high The RC is nomenclature for Round Cartridge Each series offers standard factory assembled collec...

Страница 10: ...is greater than the standard 20 w g design pressure is anticipated lb kg 2RC4 1662 754 2RC8 1763 800 2RC16 2565 1164 2RC24 4328 2072 3RC6 1999 907 3RC12 2103 954 3RC24 3123 1417 3RC36 4205 1908 3RC48...

Страница 11: ...Safe and efficient operation of the collector depends on proper installation Know proper laws codes and regulations before installation starts 5 2 Receiving Remove crates tarps shipping straps etc alo...

Страница 12: ...ING 6 1 Unloading and lifting into position Failure to lift the collector correctly can result in severe personal injury property damage or even death Connect lifting sling to all supplied lifting lug...

Страница 13: ...ed easily See collector drawing for cartridge clearance In the case of hazardous dust consult your local authorities laws codes or regulations for the location of the unit 8 2 Foundations The OptiFlo...

Страница 14: ...multiple modules normally have their housings factory pre assembled up to a minimum of 4 modules with legs and hoppers sent for site assembly If more than 4 modules are required or if there are site...

Страница 15: ...inst each other with no bulges 9 2 4 1 Leg structure Assemble the leg structure onto the prepared foundations or steelwork using the supplied GA drawing which shows the position of all the legs and cr...

Страница 16: ...re within 15ft of the static taps located on either of the OptiFlo RC side panels Usually the Pressure Demand controller is fixed to the leg structure but it can be remotely located if desired Once th...

Страница 17: ...il air tight 9 2 8 Installation of accessories When accessories such as sprinklers abrasion resistant inlets and airlocks are ordered with the OptiFlo RC separate installation instructions will be pro...

Страница 18: ...electrical connection diagram that is supplied with the specific OptiFlo RC collector ordered The power requirements are 85 270V 50 60Hz 1Ph The operating temperature range is 40F to 140F Continuous c...

Страница 19: ...is factory set at a 30 second pulse interval Do not use over 100 psig of compressed air Solenoid valves will not operate and can cause damage to collector components The compressed air connection shou...

Страница 20: ...the explosion vent during shipping or handling The OptiFlo RC will have a frame constructed as part of the unit where the explosion vent is mounted The number of explosion vents and location of the ex...

Страница 21: ...Sensor All standard explosion vents come with a burst sensor This can be connected to an AAF Control Center or to the customer s controls to shut down the unit when an event occurs The magnetic sensor...

Страница 22: ...psig Check that cartridges are properly installed and that the red cam lock handles on the port hole doors are all fully engaged see Section 9 2 7 Ensure the hopper discharge device s if any is operat...

Страница 23: ...tomatic and does not require constant supervision The OptiFlo RC is assumed to be part of a system that will include a fan and possibly other components supplied by AAF or other companies For successf...

Страница 24: ...ad on the display of the pulse controller After start up the dust collector s differential pressure should settle to approximately 2 3 inches w g The filter cleaning cycle is automatically controlled...

Страница 25: ...ir or dust leakage Check for evidence of moisture or dust build up within the collector Moisture in the collector can cause plugging and premature cartridge failure Check all electrical apparatus for...

Страница 26: ...llector Do not operate the dust collector with missing or damaged cartridges The working area requires good ventilation Some applications involve hazardous gasses and dusts Check with an authorized pe...

Страница 27: ...pping storage or handling DO NOT use damaged cartridges 8 Slide the new cartridges onto the support mandrels normally two cartridges per mandrel gasket end first While installing cartridges be careful...

Страница 28: ...ary valve etc referring to the relevant IOM and taking all safety precautions Issue Moisture Condensation Solution Free moisture on the cartridges will inhibit dust release and cause high differential...

Страница 29: ...on Ensure filter access door knob is tightened fully and the gasket appears to be air tight Perform a paper test by trying to slide a piece of paper between the gasket and unit surface If a piece of p...

Страница 30: ...ck in the hopper Solution Consider changing the process so that less moisture is drawn into the OptiFlo or that some warm dry air is included in the extraction system to drive the combined flow furthe...

Страница 31: ...moisture present in collector Date Examine cartridges Examine outer door gasket Examine inner door gasket Check correct electrical operation Examine dust disposal equipment Examine auxiliary equipment...

Отзывы: