Start Up Conditions

CONDENSATION

Whenever the water heater is filled with cold water, a cer-

tain amount of condensation will form while the burner is

on. A water heater may appear to be leaking when in fact

the water is condensing. This usually happens when:

a. When a new water heater is filled with cold water for

the first time.

b. When gas burns and water vapor is produced in water

heaters, particularly high efficiency models where flue

temperatures are lower.

c. When you use large amounts of hot water in a short

time and the refill water is very cold.

Moisture from the products of combustion condenses on

the cooler tank surfaces and form drops of water which

may fall onto the burner or other hot surfaces and produce

a “sizzling” or “frying” noise.

Because of the suddenness and amount of water, conden-

sation water may be diagnosed as a “tank leak”. After the

water in the tank warms up (about 1-2 hours), the condition

should disappear.

Do not assume the water heater is leaking until there has

been enough time for the water in the tank to warm up.

An undersized water heater will cause more condensation.

The water heater must be sized properly to meet the fami-

ly’s demands for hot water including dishwashers, wash-

ing machines and shower heads.

Excessive condensation may be noticed during the winter

and early spring months when incoming water tempera-

tures are at their lowest.

Good venting is essential for a gas fired water heater to

operate properly as well as to carry away products of com-

bustion and water vapor.

SMOKE/ODOR

It is not uncommon to experience a small amount of smoke

and odor during the initial start-up. This is due to burning

off of oil from metal parts, and will disappear in a short

while.

THERMAL EXPANSION

Water supply systems may, because of such events as high

line pressure, frequent cut-offs, the effects of water ham-

mer among others, have installed devices such as pressure

reducing valves, check valves, back flow preventers,

etc...to control these types of problems. When these

devices are not equipped with an internal by-pass, and no

other measures are taken, the devices cause the water sys-

tem to be closed. As water is heated, it expands (thermal

expansion) and closed systems do not allow for the expan-

sion of heated water.

The water within the water heater tank expands as it is

heated and increases the pressure of the water system. If

the relieving point of the water heaters temperature-pres-

sure relief valve is reached, the valve will relieve the excess

pressure. 

The temperature-pressure relief valve is not

intended for the constant relief of thermal expansion.

This

is an unacceptable condition and must be corrected.

It is recommended that any devices installed which could

create a closed system have a by-pass and/or the system

have an expansion tank to relieve the pressure built by ther-

mal expansion in the water system. Expansion tanks are

available for ordering through local plumbing supply hous-

es. Contact the local water supplier and/or plumbing

inspector for assistance in controlling these situations.

STRANGE SOUNDS

Possible noises due to expansion and contraction of some

metal parts during periods of heat-up and cool-down do

not represent harmful or dangerous conditions.
Condensation causes sizzling and popping with the burn-

er area during heating and cooling periods and should be

considered normal. See “Condensation” in this section.

Operational Conditions

SMELLY WATER

In each water heater there is installed at least one anode

rod (see parts section) for corrosion protection of the tank.

Certain water conditions will cause a reaction between this

rod and the water. The most common complaint associat-

ed with the anode rod is one of a “rotten egg smell”. This

odor is derived from hydrogen sulfide gas dissolved in the

water. The smell is the result of four factors which must all

be present for the odor to develop:

a. a concentration of sulfate in the supply water.

b. little or no dissolved oxygen in the water.

c. a sulfate reducing bacteria within the water heater.

(This harmless bacteria is non-toxic to humans.)

d. an excess of active hydrogen in the tank. This is

caused by the corrosion protective action of the

anode.

Smelly water may be eliminated or reduced in some water

heater models by replacing the anode(s) with one of less

active material, and then chlorinating the water heater tank

and all hot water lines. Contact the local water heater sup-

plier for further information concerning an Anode

Replacement Kit #9000029 and this Chlorination

Treatment.

For Your Information

29

Содержание Residential Power Vent Gas Water Heaters with Hot Surface...

Страница 1: ...s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the info...

Страница 2: ...r is detected follow steps indicated at For Your Safety on the cover page of this manual then leave the premises WARNING Improper installation adjustment alteration service or main tenance can cause d...

Страница 3: ...as regulating equipment WARNING Obstructed or deteriorated vent systems may present a serious health risk or asphyxiation WARNING Chemical vapor corrosion of the flue and vent system may occur if air...

Страница 4: ...2 Gas Piping 22 23 Installation Checklist 24 Operating 25 27 Temperature Regulation 28 For Your Information 29 30 Start Up Conditions 29 Condensation 29 Smoke Odor 29 Thermal Expansion 29 Strange Soun...

Страница 5: ...operate properly It could cause DEATH SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE This manual contains instructions for the installation operation and maintenance of the gas fired water heater It als...

Страница 6: ...RGE PIPE Do not cap or plug PROVIDE A 6 AIR GAP BETWEEN THE END OF THE DISCHARGE PIPE AND DRAIN 7 power cord Factory supplied Some models are equipped with circulating loop fittings WARNING This water...

Страница 7: ...ions cannot be avoided a suitable drain pan should be installed under the water heater Drain pans are available at your local hardware store Such a drain pan must be not greater than 11 2 inches deep...

Страница 8: ...7 Y 3 1 LgN N LgV 1 g XgN J H N L 1g 3 3 L 1g N Lg 1g 3 7 5 3 1 e L f V N 1 h3 X f L f N J H N e3 1 gN L L gN 1 f 1 g3 7 L eV Lg 3 3 1 Xg 3 Lf LgN 5 3 1 e N X f N N 1g N X e H V 1g 3 J H N f3 1 g3 3...

Страница 9: ...r servicing and proper operation of the water heater Figure 4 The venting system must be installed in a manner which allows inspection of the installation of the venting pipes and joints as well as pe...

Страница 10: ...total input rating of all equipment in the enclosure See Figure 9 4 When ducts are used they shall be of the same cross sec tional area as the free area of the openings to which they connect The mini...

Страница 11: ...apter to the cold water inlet con nection Do not solder the cold water supply line directly to the cold water inlet or it will harm the dip tube NOTE This water heater is insulated to minimize heat lo...

Страница 12: ...art The discharge opening must not be blocked or reduced in size under any circumstances Excessive length over 30 feet or use of more than four elbows can cause restriction and reduce the discharge ca...

Страница 13: ...ters junction box 7 MAXIMUM CORD LENGTH Factory supplied You must provide all wiring of the proper size outside of the water heater You must obey local codes and electric company requirements when you...

Страница 14: ...n box Connect ground wire to this location For complete grounding details and all allowable exceptions refer to local codes or in the absence of local codes with the National Electrical Code ANSI NFPA...

Страница 15: ...er heater the correct vent pipe diameter must be utilized Do not install any other gas appliances on the same vent with this water heater as this will adversely affect the operation of the water heate...

Страница 16: ...VC ABS or CPVC Schedule 40 reducer must be supplied locally 5 A 4 PVC ABS or CPVC Schedule 40 90 street ell used to connect the vent pipe to the reducer when the vent pipe is to be turned horizontally...

Страница 17: ...CPVC Schedule 40 reducer must be supplied locally 5 A 2 PVC ABS or CPVC Schedule 40 90 street ell used to connect the vent pipe to the reducer when the vent pipe is to be turned horizontally off the...

Страница 18: ...AX LENGTH FT 90 ELBOWS 70 1 65 2 60 3 55 4 50 5 45 6 ALL 40 and 50 GALLON 40 000 BTU HR MODELS ONLY 3 DIA VENT NUMBER OF MAX LENGTH FT 90 ELBOWS 115 1 110 2 105 3 100 4 95 5 90 6 ALL 40 and 50 GALLON...

Страница 19: ...e them near heat sparks or flames Keep containers closed Use them in well ventilated areas Wear impervious clothing while handling Do not smoke eat or drink while handling Wash thoroughly after handli...

Страница 20: ...E When determining location of the opening in the outside wall allow for the 1 8 rise per five feet that has taken place in the horizontal run MIN RISE 1 8 PER FIVE FEET C L OF FLUE 40 GAL 60 50 GAL 5...

Страница 21: ...3 TO 2 PVC ABS OR CPVC REDUCER 4 If the optional 4 vent piping is to be used 50 000 BTU Hr and higher models only the 4 street elbow 4 to 3 reducer and 3 minimum section of 3 PVC ABS or CPVC pipe mus...

Страница 22: ...EARANCE EXHAUST VERTICAL VENT CERTIFIED WATER HEATER TOTAL VERTICAL AND HORIZONTAL RUNS SEE ITEM 6 45 VENT CAP 90 STREET ELL 6 The total vertical and horizontal vent run cannot exceed the maximum leng...

Страница 23: ...VALVE GROUND JOINT UNION BLACK PIPE DRIP LEG SEDIMENT TRAP CAP 3 MIN 3 MIN A gas line of sufficient size must be run to the water heater Consult the current edition of National Fuel Gas Code ANSI Z223...

Страница 24: ...r heater completely filled with water See Filling the Water Heater instructions in the Installing the New Water Heater section 5 Will a water leak damage anything See the Locating the New Water Heater...

Страница 25: ...mation section 4 There is a non resettable hi limit switch in the thermo stat which must be good closed for the thermostat to be operated See High Temperature Shut Off System in the For Your Informati...

Страница 26: ...s by sniffing at ground level in the vicinity of the appliance If odor is detected follow the steps indicated at For Your Safety on the cover page of this manual then leave the premises WARNING AN ODO...

Страница 27: ...essing the COOLER and HOTTER buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the control box to the OFF positio...

Страница 28: ...you must take special precautions In addition to using the lowest possible temperature setting that satisfies your hot water needs some type of tempering device such as a mixing valve should be used...

Страница 29: ...hermal expansion and closed systems do not allow for the expan sion of heated water The water within the water heater tank expands as it is heated and increases the pressure of the water system If the...

Страница 30: ...ormation cont d SMELLY WATER cont d If the smelly water persists after the anode replacement and chlorination treatment we can only suggest that continuous chlorination and filtering conditioning equi...

Страница 31: ...calcium and sodium chloride waxes bleach and process chemicals are typical compounds which are potentially corrosive WARNING Obstructions and deteriorated vent systems may present serious health risk...

Страница 32: ...ay be due to thermal expansion Your water heater may have a check valve installed in the water line or a water meter with a check valve Consult the water supplier and or plumbing contractor for furthe...

Страница 33: ...drain valve should be left open with hose connected allowing water to ter minate to an adequate drain 6 Close the drain valve 7 Follow instructions in the Filling The Water Heater section 8 Follow the...

Страница 34: ...This is common at the time of startup after installation and when incoming water is cold Water in the water heater bottom or on the floor may be from condensation loose connections or the relief valve...

Страница 35: ...roper and possible danger ous operation resulting in DEATH SERIOUS BODILY INJURY OR PROPERTY DAMAGE THERMOSTAT AND GAS SUPPLY CHECK Is thermostat calling for heat Run hot water from heater and set adj...

Страница 36: ...intake or exhaust obstructed Error in the hot surface ignitor circuit 1 Check that all wiring is correct and secure 2 Replace hot surface ignitor System in lockout 1 Gas supply is off or too low to o...

Страница 37: ...st venting and YELLOW FLAME air openings in bottom base pan for obstructions or blockage C Not enough dilution air for proper Check dilution air intake for obstructions or combustion blockage A Water...

Страница 38: ...Parts 1 2 3 4 5 7 8 9 10 11 21 12 14 13 15 17 16 23 22 20 24 25 26 27 28 29 30 18 19 6 PVC ABS or CPVC items for all models supplied locally or OR 8 9 Blower Draft Hood Assembly for 40 000 Btu Hr Mod...

Страница 39: ...from or the manufacturer listed on the model rating plate on the water heater Be sure to provide all pertinent facts when you call or visit Selling prices will be furnished on request or parts will b...

Страница 40: ......

Отзывы: