Menu

: The left Operational Button is pressed to enter the Main Menu 

where all control system menus are accessed. See Table 3 for a list 

of control system menus.

Help: 

The right Operational Button is pressed to access instructions 

and explanations for user settings, Operating States, Status Icons, 

manufacturer’s web address, technical support phone number and 

service agent contact information.

Day/Time/Operating  Mode:

  The  current  time  and  day  are 

also displayed on the Desktop Screen. “Clock Not Set” will be 

displayed until the time clock has been initially set. Day and Time 

are  adjusted  in  the  Economy  Mode  Setup  menu.  The  current 

Operating  Mode,  either  Normal  Mode  or  Economy  Mode,  is 

displayed beneath the day and time.

Discreet Menu Contact Information:

 From the Desktop Screen 

press and hold down the middle (unmarked) Operational Button for 

30 seconds and then release it. This will launch a discreet menu 

where personalized contact information can be entered. Installing 

contractors and/or service agents can enter their company name 

and telephone number. This contact information will be displayed 

with all Fault and Alert messages.

Icon

descrIptIon

Water temperature in the tank has fallen. Shaded area of the animated thermometer icon will rise and fall in 

response to water temperature in the storage tank as sensed from the immersion Temperature Probe.

Water temperature in the tank has reached the Operating Set Point. Shaded area of the animated thermometer 

icon  will  rise  and  fall  in  response  to  water  temperature  in  the  storage  tank  as  sensed  from  the  immersion 

Temperature Probe.

The control is unable to initiate a heating cycle. This will happen whenever a Fault condition is detected by the 

control system or when either of the two Enable/Disable circuits are open circuits.

The control system is in Heating Mode and has energized the electromagnetic contactor coils for at least one bank 

of heating elements. This animated icon DOES NOT indicate current has been sensed from the heating elements, 

only that there is a call for heat present and the control system has initiated heating operation.

Heating elements icon for a water heater equipped with 1 Bank of heating elements. Each circle represents one 

heating element. Each diagonal row of 3 elements = 1 Bank of elements. Open circles represent heating elements 

the control system has not energized and is not sensing electrical current from.

Heating elements icon for a water heater equipped with 2 Banks of heating elements. Each circle represents one 

heating element. Each diagonal row of 3 elements = 1 Bank of elements. Open circles represent heating elements 

the control system has not energized and is not sensing electrical current from.

Heating elements icon for a water heater equipped with 3 Banks of heating elements. Each circle represents one 

heating element. Each diagonal row of 3 elements = 1 Bank of elements. Open circles represent heating elements 

the control system has not energized and is not sensing electrical current from.

Heating elements icon for a water heater equipped with 3 Banks of heating elements. Each circle represents one 

heating element. Each diagonal row of 3 elements = 1 Bank of elements. Filled circles represent heating elements 

the control system has energized AND is sensing electrical current from.

Heating elements icon for a water heater equipped with 3 Banks of heating elements. Each circle represents one 

heating element. Each diagonal row of 3 elements = 1 Bank of elements. Open circles with an X represent heating 

elements the control system has energized that it IS NOT sensing electrical current from.

The control has detected/declared a Fault Condition. Fault message details can be viewed in the Current Fault 

menu. Heating operation is discontinued (locked out) until the condition that caused the fault is corrected. Power to 

the water heater must be cycled off and on to reset the control system. Note; cycling power will not reset the control 

system if the condition that caused the fault has not been corrected.

The control has detected/declared an Alert Condition. The water heater will continue to operate during an Alert 

Condition but there is an operational condition that requires the attention of a Qualified Service Agent. Alert message 

details can be viewed in the Current Alert menu.

taBle 1 status Icons.

Содержание DURA-Power DRE-52

Страница 1: ...uture reference COMMERCIAL ELECTRIC WATER HEATERS Thank you for buying this energy efficient water heater We appreciate your confidence in our products MODELS DRE 52 80 120 SERIES 100 DVE 52 80 120 SE...

Страница 2: ...ing or replacement of gas piping or b the connection installation testing repair or servicing of appliances and equipment that is experienced in such work that is familiar with all precautions require...

Страница 3: ...ay also cause erratic control system operation on ELECTRONIC CONTROL models This water heater must be connected to a grounded metal permanent wiring system or an equipment grounding conductor must be...

Страница 4: ...ian StandardsAssociation 8501 East Pleasant Valley Road Cleveland OH 44131 3 If after reading this manual you have any questions or do not understand any portion of the instructions call the toll free...

Страница 5: ...ed to as Electronic Control models RECOVERY RATE IN GALLONS PER HOUR Temperature Rise F Standard KW Input BTU Hour 30 40 50 60 70 80 90 100 110 120 130 140 6 20 478 82 62 49 41 35 31 27 25 22 21 19 18...

Страница 6: ...6 APPROVALS MODEL AND RATING All models meet National Sanitation Foundation NSF 5 requirements All models are listed by Underwriters Laboratories Inc...

Страница 7: ...7 FEATURES AND COMPONENTS ELECTRONIC CONTROL MODELS FIGURE 1...

Страница 8: ...8 FEATURES AND COMPONENTS SURFACE MOUNT CONTROL MODELS FIGURE 2...

Страница 9: ...ank or connections will not result in damage to the area adjacent to the heater or to lower floors of the structure 3 Close to the point of major hot water usage and the power supply Hot water piping...

Страница 10: ...n to using the lowest possible temperature setting that satisfies your hot water needs a means such as a MIXING VALVE should be used at the hot water taps used by these people or at the water heater M...

Страница 11: ...relief valve must be manually operated at least once a year Caution should be taken to ensure that 1 no one is in front of or around the outlet of the temperature pressure relief valve discharge line...

Страница 12: ...tection and disconnect switch The water heater should be grounded in accordance with national and local codes Voltage applied to the heater should not vary more than 5 to 10 of the model and rating pl...

Страница 13: ...ace information display and element current sensors for monitoring the power circuits Refer to the control circuit label on the water heater for details The CCB ispoweredbyasmall120V 24Vtransformer Th...

Страница 14: ...14 CCB CENTRAL CONTROL BOARD CIRCUIT BOARD CONTROL CIRCUIT DIAGRAM ELECTRONIC CONTROL MODELS FIGURE 3 WIRING DIAGRAMS...

Страница 15: ...the heater circuits and includes wiring diagrams All heater circuits are designed for 60 50 hertz alternating current The water heater circuit wiring is 12 AWG AWM or TEW type rated 600 volts 105 C F...

Страница 16: ...to terminal L1 with black wires 3 Reconnect all yellow wires to terminal L2 with red wires 4 Connect incoming power to terminals L1 and L2 CONVERSION TO THREE PHASE When heater is shipped for connect...

Страница 17: ...page 8 The following describes the heater circuits and includes wiring diagrams All heater circuits are designed for 60 50 hertz alternating current The water heater circuit wiring is 12 AWG AWM or T...

Страница 18: ...ect all red wires to terminal L 2 with yellow wires 5 Connect incoming power to terminals L1 and L2 CONVERSION TO THREE PHASE When heater is shipped for connection to a single phase electrical service...

Страница 19: ...d electrical connections for tightness Also check connections on top and side of heater Repair water leaks and tighten electrical connections as necessary 3 Depress the red manual reset button on each...

Страница 20: ...when the water temperature reaches approximately 202 F 94 C When the ECO switch contacts open activate the electronic control system locks out and displays a Fault message Voltage to the contactor coi...

Страница 21: ...adjustable 1 to 20 differential set points for each bank First bank on is the last bank off Helps reduce operating costs during low moderate loads CONTROL SYSTEM NAVIGATION The UIM User Interface Modu...

Страница 22: ...control system has initiated heating operation Heating elements icon for a water heater equipped with 1 Bank of heating elements Each circle represents one heating element Each diagonal row of 3 elem...

Страница 23: ...played in this menu Economy Mode Setup Seven day 24 hour time clock with temperature set back capability to reduce operating costs during unoccupied or reduced demand periods Alarm Output Setup The co...

Страница 24: ...g This can improve the precision of temperature control in the storage tank and at points of use This feature can also be used to compensate for building recirculation loops hot water returning to the...

Страница 25: ...on off status of each Bank of heating elements Yes On No Off Alarm Condition Displays the status of the user definable Alarm Output function see Alarm Output Setup Menu Yes alarm condition has been m...

Страница 26: ...tional Buttons on the display changes as you navigate through the various menus and screens Use the Up Down buttons to select highlight in black the Economy Mode Setup menu from the Main Menu Press th...

Страница 27: ...ges to ACCEPT CANCEL when the adjustment mode is activated and how the current setting is outlined rather than highlighted in black Press the Operational Button underneath ACCEPT to enter and confirm...

Страница 28: ...Up Down and CHANGE buttons to enter the Mon sub menu Use the Up Down buttons to select highlight in black the Normal Operation Between setting Press the Operational Button underneath SELECT to change...

Страница 29: ...n current tank temperature drops below programmable Alarm SP Fault or Alert Used for external notification whenever a Fault or Alert condition is active Fault Used for notification whenever a Fault co...

Страница 30: ...sages in chronological order in this menu The most recent will be at the top of the list A time stamp is displayed below each listed Fault and Alert message showing when the Fault or Alert condition o...

Страница 31: ...the drain valve should be opened and the water allowed to run until it flows clean This will help to prevent sediment buildup in the tank bottom Periodically check the temperature and pressure relief...

Страница 32: ...lements should be examined regularly Lime scale accumulations may cause noises to occur during operation It is recommended that a heating element be removed periodically for examination If it is scale...

Страница 33: ...ed See the Maintenance section of this manual 2 Some of the electrical components of the water heater make sounds which are normal Contactors will click or snap as the heater starts and stops Transfor...

Страница 34: ...ters tank insert Q tip or similar absorbent material between jacket opening and valve to swab spud area Remove valve if leak is indicated and repair with pipe joint compound Water on the side of the t...

Страница 35: ...35 PIPING DIAGRAMS ONE TEMPERATURE WITH CIRCULATING LOOP INSERT B VACUUM RELIEF VALVE INSTALL PER LOCAL CODES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH ALL LOCAL CODES...

Страница 36: ...36 PIPING DIAGRAMS INSERT B VACUUM RELIEF VALVE INSTALL PER LOCAL CODES...

Страница 37: ...37 PIPING DIAGRAMS INSERT B VACUUM RELIEF VALVE INSTALL PER LOCAL CODES...

Страница 38: ...OCAL CODES ONE TEMPERATURE ONE HEATER VERTICAL STORAGE TANK FORCED CIRCULATION WITHOUT BUILDING RECIRCULATION TWO TEMPERATURE WITH MIXING VALVE AND CIRCULATING LOOP TWO TEMPERATURE WITH MIXING VALVE P...

Страница 39: ...39 PIPING DIAGRAMS TWO HEATERS WITH HORIZONTAL STORAGE TANK WITH OR WITHOUT BUILDING RECIRCULATION INSERT B VACUUM RELIEF VALVE INSTALL PER LOCAL CODES...

Страница 40: ...S THREE HEATERS WITH HORIZONTAL STORAGE TANK WITH OR WITHOUT BUILDING RECIRCULATION THREE HEATERS WITH VERTICAL STORAGE TANK WITH OR WITHOUT BUILDING RECIRCULATION INSERT B VACUUM RELIEF VALVE INSTALL...

Страница 41: ...MS FOUR HEATERS WITH VERTICAL STORAGE TANK WITH OR WITHOUT BUILDING RECIRCULATION FOUR HEATERS WITH HORIZONTAL STORAGE TANK WITH OR WITHOUT BUILDING RECIRCULATION INSERT B VACUUM RELIEF VALVE INSTALL...

Страница 42: ...2 Inlet and outlet size 1 1 2 THREE HEATERS Tank Capacity gallons Part Number H W D A 52 9003430205 66 1 4 91 3 4 27 1 4 13 1 4 80 9003430205 70 1 2 95 1 4 31 1 4 9 3 4 120 9003430205 73 1 4 99 1 2 35...

Страница 43: ...he owner is responsible for all other costs Such costs may include but are not limited to a Labor charges for service removal repair or reinstallation of the water heater or any component part b Shipp...

Страница 44: ...44 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Отзывы: