13

aMperaGe taBle/oVercurrent protectIon

The tables above provides the total connected heating element load 

in amperes for branch circuit conductor and overcurrent protection 

sizing.  Single-phase  heaters  are  two  wire  circuits. Three-phase 

heaters  are  three  wire  circuits.  In  addition  to  the  foregoing,  a 

grounded conductor is required.
The rating of the overcurrent protection must be computed on the basis 

of 125% of the total connected load amperage. Where the standard 

ratings and settings do not correspond with this computation, the next 

higher standard rating or setting should be selected.

heater cIrcuIts - electronIc control Models

The water heater’s electrical components are pictured and identified 

in Figures 1 and 2. The model and rating plate illustration on page 4 

identifies heater circuit ratings. The ELECTRONIC CONTROL model 

has two electrical circuits.
•  The control circuit, which controls the electrical power to heating

 

  elements, referring the following control circuit diagram Figure 3.
•  The power circuit, which is operated by the control circuit carries

 

  the  electrical  load  of  the  heating  elements.  The  following

 

  describes the heater circuits and includes wiring diagrams for

 

  Delta configuration, refer to the “WYE Configuration Insert” for

 

  water heaters operating at 380V/400V/416V/575V. All heater

 

  circuits are designed for 50/60 cycle alternating current.

control cIrcuIt - electronIc control Models

These models are equipped with an electronic control system. The 

system  includes  a  CCB  (Central  Control  Board)  circuit  board,  an 

immersion temperature probe with ECO for temperature sensing and 

limiting, a UIM (User Interface Module) for user interface & information 

display and element current sensors for monitoring the power circuits. 

Refer to the control circuit label on the water heater for details. The CCB 

is powered by a small 120V/24V transformer. The control circuit operates 

on 120V supplied by a larger 100VA transformer. Standard equipment 

includes control circuit fusing using two, 3 amp, class G fuses with 600 

volt rating. Do not substitute fuses of a different rating.

Sequence of Operation
1. When  the  control  is  powered,  the  UIM  should  display  model

 

  information,  water  temperature,  Operating  Set  Point,  heating

 

  status and operating mode.

2. If the control determines that the actual water temperature inside

 

  the tank is below the programmed Operating Setpoint minus the (1st)

 

  differential, a call for heat is activated.

3. After all safety checks are verified, the CCB will energize contactor

 

  coils starting with the lower bank of heating elements (each 

 

  diagonal row of three heating elements is considered a “bank” - see

 

  Figure 1) then energize the middle bank (if so equipped) and top bank

 

  (if so equipped). The middle and top banks (if so equipped) are

 

  energized according to programmed 2nd and 3rd differential

 

  set points. 

4. The control remains in the heating mode until the water temperature

 

  reaches  the  programmed  Operating  Setpoint. At  this  point  the

 

  contactors will be de-energized in the reverse order.

5. The control system now enters the standby operating mode while

 

  continuing to monitor the water temperature and the state of other

 

  system  devices.  If  the  water  temperature  drops  below  the

 

  programmed Operating Setpoint minus the (1st) differential, the control

 

  will automatically return to step 2 and repeat the heating cycle. 
NOTE: See the Electronic Control Models Operation section for more 

detailed information on temperature settings mentioned above.

120 Vac control cIrcuIt transforMer connectIons - electronIc control Models

Содержание DURA-Power DRE-52

Страница 1: ...uture reference COMMERCIAL ELECTRIC WATER HEATERS Thank you for buying this energy efficient water heater We appreciate your confidence in our products MODELS DRE 52 80 120 SERIES 100 DVE 52 80 120 SE...

Страница 2: ...ing or replacement of gas piping or b the connection installation testing repair or servicing of appliances and equipment that is experienced in such work that is familiar with all precautions require...

Страница 3: ...ay also cause erratic control system operation on ELECTRONIC CONTROL models This water heater must be connected to a grounded metal permanent wiring system or an equipment grounding conductor must be...

Страница 4: ...ian StandardsAssociation 8501 East Pleasant Valley Road Cleveland OH 44131 3 If after reading this manual you have any questions or do not understand any portion of the instructions call the toll free...

Страница 5: ...ed to as Electronic Control models RECOVERY RATE IN GALLONS PER HOUR Temperature Rise F Standard KW Input BTU Hour 30 40 50 60 70 80 90 100 110 120 130 140 6 20 478 82 62 49 41 35 31 27 25 22 21 19 18...

Страница 6: ...6 APPROVALS MODEL AND RATING All models meet National Sanitation Foundation NSF 5 requirements All models are listed by Underwriters Laboratories Inc...

Страница 7: ...7 FEATURES AND COMPONENTS ELECTRONIC CONTROL MODELS FIGURE 1...

Страница 8: ...8 FEATURES AND COMPONENTS SURFACE MOUNT CONTROL MODELS FIGURE 2...

Страница 9: ...ank or connections will not result in damage to the area adjacent to the heater or to lower floors of the structure 3 Close to the point of major hot water usage and the power supply Hot water piping...

Страница 10: ...n to using the lowest possible temperature setting that satisfies your hot water needs a means such as a MIXING VALVE should be used at the hot water taps used by these people or at the water heater M...

Страница 11: ...relief valve must be manually operated at least once a year Caution should be taken to ensure that 1 no one is in front of or around the outlet of the temperature pressure relief valve discharge line...

Страница 12: ...tection and disconnect switch The water heater should be grounded in accordance with national and local codes Voltage applied to the heater should not vary more than 5 to 10 of the model and rating pl...

Страница 13: ...ace information display and element current sensors for monitoring the power circuits Refer to the control circuit label on the water heater for details The CCB ispoweredbyasmall120V 24Vtransformer Th...

Страница 14: ...14 CCB CENTRAL CONTROL BOARD CIRCUIT BOARD CONTROL CIRCUIT DIAGRAM ELECTRONIC CONTROL MODELS FIGURE 3 WIRING DIAGRAMS...

Страница 15: ...the heater circuits and includes wiring diagrams All heater circuits are designed for 60 50 hertz alternating current The water heater circuit wiring is 12 AWG AWM or TEW type rated 600 volts 105 C F...

Страница 16: ...to terminal L1 with black wires 3 Reconnect all yellow wires to terminal L2 with red wires 4 Connect incoming power to terminals L1 and L2 CONVERSION TO THREE PHASE When heater is shipped for connect...

Страница 17: ...page 8 The following describes the heater circuits and includes wiring diagrams All heater circuits are designed for 60 50 hertz alternating current The water heater circuit wiring is 12 AWG AWM or T...

Страница 18: ...ect all red wires to terminal L 2 with yellow wires 5 Connect incoming power to terminals L1 and L2 CONVERSION TO THREE PHASE When heater is shipped for connection to a single phase electrical service...

Страница 19: ...d electrical connections for tightness Also check connections on top and side of heater Repair water leaks and tighten electrical connections as necessary 3 Depress the red manual reset button on each...

Страница 20: ...when the water temperature reaches approximately 202 F 94 C When the ECO switch contacts open activate the electronic control system locks out and displays a Fault message Voltage to the contactor coi...

Страница 21: ...adjustable 1 to 20 differential set points for each bank First bank on is the last bank off Helps reduce operating costs during low moderate loads CONTROL SYSTEM NAVIGATION The UIM User Interface Modu...

Страница 22: ...control system has initiated heating operation Heating elements icon for a water heater equipped with 1 Bank of heating elements Each circle represents one heating element Each diagonal row of 3 elem...

Страница 23: ...played in this menu Economy Mode Setup Seven day 24 hour time clock with temperature set back capability to reduce operating costs during unoccupied or reduced demand periods Alarm Output Setup The co...

Страница 24: ...g This can improve the precision of temperature control in the storage tank and at points of use This feature can also be used to compensate for building recirculation loops hot water returning to the...

Страница 25: ...on off status of each Bank of heating elements Yes On No Off Alarm Condition Displays the status of the user definable Alarm Output function see Alarm Output Setup Menu Yes alarm condition has been m...

Страница 26: ...tional Buttons on the display changes as you navigate through the various menus and screens Use the Up Down buttons to select highlight in black the Economy Mode Setup menu from the Main Menu Press th...

Страница 27: ...ges to ACCEPT CANCEL when the adjustment mode is activated and how the current setting is outlined rather than highlighted in black Press the Operational Button underneath ACCEPT to enter and confirm...

Страница 28: ...Up Down and CHANGE buttons to enter the Mon sub menu Use the Up Down buttons to select highlight in black the Normal Operation Between setting Press the Operational Button underneath SELECT to change...

Страница 29: ...n current tank temperature drops below programmable Alarm SP Fault or Alert Used for external notification whenever a Fault or Alert condition is active Fault Used for notification whenever a Fault co...

Страница 30: ...sages in chronological order in this menu The most recent will be at the top of the list A time stamp is displayed below each listed Fault and Alert message showing when the Fault or Alert condition o...

Страница 31: ...the drain valve should be opened and the water allowed to run until it flows clean This will help to prevent sediment buildup in the tank bottom Periodically check the temperature and pressure relief...

Страница 32: ...lements should be examined regularly Lime scale accumulations may cause noises to occur during operation It is recommended that a heating element be removed periodically for examination If it is scale...

Страница 33: ...ed See the Maintenance section of this manual 2 Some of the electrical components of the water heater make sounds which are normal Contactors will click or snap as the heater starts and stops Transfor...

Страница 34: ...ters tank insert Q tip or similar absorbent material between jacket opening and valve to swab spud area Remove valve if leak is indicated and repair with pipe joint compound Water on the side of the t...

Страница 35: ...35 PIPING DIAGRAMS ONE TEMPERATURE WITH CIRCULATING LOOP INSERT B VACUUM RELIEF VALVE INSTALL PER LOCAL CODES PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH ALL LOCAL CODES...

Страница 36: ...36 PIPING DIAGRAMS INSERT B VACUUM RELIEF VALVE INSTALL PER LOCAL CODES...

Страница 37: ...37 PIPING DIAGRAMS INSERT B VACUUM RELIEF VALVE INSTALL PER LOCAL CODES...

Страница 38: ...OCAL CODES ONE TEMPERATURE ONE HEATER VERTICAL STORAGE TANK FORCED CIRCULATION WITHOUT BUILDING RECIRCULATION TWO TEMPERATURE WITH MIXING VALVE AND CIRCULATING LOOP TWO TEMPERATURE WITH MIXING VALVE P...

Страница 39: ...39 PIPING DIAGRAMS TWO HEATERS WITH HORIZONTAL STORAGE TANK WITH OR WITHOUT BUILDING RECIRCULATION INSERT B VACUUM RELIEF VALVE INSTALL PER LOCAL CODES...

Страница 40: ...S THREE HEATERS WITH HORIZONTAL STORAGE TANK WITH OR WITHOUT BUILDING RECIRCULATION THREE HEATERS WITH VERTICAL STORAGE TANK WITH OR WITHOUT BUILDING RECIRCULATION INSERT B VACUUM RELIEF VALVE INSTALL...

Страница 41: ...MS FOUR HEATERS WITH VERTICAL STORAGE TANK WITH OR WITHOUT BUILDING RECIRCULATION FOUR HEATERS WITH HORIZONTAL STORAGE TANK WITH OR WITHOUT BUILDING RECIRCULATION INSERT B VACUUM RELIEF VALVE INSTALL...

Страница 42: ...2 Inlet and outlet size 1 1 2 THREE HEATERS Tank Capacity gallons Part Number H W D A 52 9003430205 66 1 4 91 3 4 27 1 4 13 1 4 80 9003430205 70 1 2 95 1 4 31 1 4 9 3 4 120 9003430205 73 1 4 99 1 2 35...

Страница 43: ...he owner is responsible for all other costs Such costs may include but are not limited to a Labor charges for service removal repair or reinstallation of the water heater or any component part b Shipp...

Страница 44: ...44 500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Отзывы: