16
•
The current flowing between the Flame Sensor and Burner is DC micro amp current expressed as: µA (micro Amps). Flame sensing
current can be measured with a DC micro amp test meter, see “Tools Recommended” on Page
SPARK
IGNITER
BURNER
FLAME
BURNER
(MUST BE GROUNDED)
CERAMIC INSULATOR
FLAME SENSOR
METAL CONDUCTOR
CONTROL SYSTEM
APPLIES AC CURRENT
TO FLAME SENSOR
AC CURRENT FLOWS FROM THE FLAME
SENSOR TO THE BURNER. THE BURNER
MUST BE GROUNDED FOR CURRENT TO
FLOW. DURING THIS PROCESS THE AC
CURRENT IS “RECTIFIED” AND BECOMES
A DC CURRENT. DC MICRO AMP CURRENT
THEN FLOWS BETWEEN THE FLAME SENSOR
AND THE BURNER.
MINIMUM FLAME SENSING CURRENT
To prove burner flame during the Ignition Verification state the Control System monitors flame sensing current, the DC micro amp (μA)
current flowing through the Flame Sensor. The Control System must sense a minimum amount of current to “prove” flame. The
minimum flame sensing current is 1.0 μA. If flame sensing current does not reach 1.0 µA during ignition or falls below this amount
during a heating cycle the Control System will immediately de-energize the 24 Volt Gas Control Valve.
After 3 failed trials for ignition the Control System will lock out and display
Ignition Failure
(fault condition) on the UIM. If flame sensing
current drops below 1.0 μA during a heating cycle the Control System will de-energize the 24 Volt Gas Control Valve and enter the
Inter-Purge operating state. After the Inter-Purge operating state the Control System will try for ignition again if a call for heat is still
Sequence of Operation Flow Chart
FLAME SENSING CURRENT TEST
During the heating cycle the flame sensing current is normally greater than 8.0 μA with a clean Flame Sensor. Over time the Flame
Sensor can degrade and this will reduce flame sensing current. With heavier use, more heating cycles/greater load, this will occur more
quickly.
Measuring flame sensing current requires a test meter with a DC micro amp function, see “Tools Recommended” on Page
meter’s selector is set to DC micro amps. The two test leads from the meter are placed in series with the flame sensing circuit. This can
be done at the spade (male/female) flame sensing wiring connectors. See Figure below.
To measure flame current disable water heating by turning off the Enable/Disable Switch located in the front of the water heater and
connect the test meter following the method shown in Figure below. Enable water heating and ensure a call for heat is active - when the
Control System energizes the 24 Volt Gas Control Valve the meter will measure flame sensing current during normal operation.
Service Notes:
•
The most common cause of
Ignition Failure
lock out is a worn Flame Sensor. The Flame Sensor should be inspected and cleaned
anytime the measured flame sensing current is below 8 µA or the Burner has been removed. Clean the Flame Sensor with ultra
fine steel wool. DO NOT use a coarse abrasive material such as sand paper. Inspect the ceramic insulator on the Flame Sensor for
cracks, replace the Flame Sensor if it is damaged.
•
An open flame sensing circuit caused by disconnected or loose connectors can also cause ignition failure. Check all wiring and wiring
connections between the Flame Sensor and the J14 connector on CCB circuit board. See
•
The Burner not being grounded will cause
Ignition Failure
Electrical Connections – All Models
heater and the Burner are properly grounded.
Содержание Cyclone XL 100 Series
Страница 41: ...41 NOTES NOTES...
Страница 42: ...42 NOTES NOTES...
Страница 43: ...43 NOTES NOTES...
Страница 44: ...44 Tech Support 800 527 1953 Parts 800 433 2545 www hotwater com Copyright 2020 All rights reserved...