INSTALLATION CONSIDERATIONS

INSTALLATION CONSIDERATIONS

This section of the Service Handbook covers some of the critical installation requirements that, when overlooked, often result in 

operational problems, down time and needless parts replacement. Costs to correct installation errors are not covered under the limited 

warranty. Ensure all installation requirements and instructions contained in the Instruction Manual that came with the water heater have 

been followed prior to performing any service procedures.

INSTRUCTION MANUAL

Have a copy of the Instruction Manual that came with the water heater on hand for the model and series number being serviced. 

Installation information given in this Service Handbook is not a complete installation instruction. Installation information given in this 

Service Handbook has a limited focus as it applies to servicing the water heater. This Service Handbook does not replace or supersede 

the Instruction Manual that came with the water heater. Always refer to the Instruction Manual for complete installation instructions. If 

the Instruction Manual is not on hand, copies can be obtained from the manufacturers web site or by calling the technical support phone 

number shown on the back cover of this Service Handbook.

CLOSED WATER SYSTEMS

Water supply systems may, because of code requirements or such conditions as high line pressure, among others, have installed 

devices such as pressure reducing valves, check valves, and back flow preventers. Devices such as these cause the water system to 

be a closed system.

THERMAL EXPANSION

As water is heated, it expands (thermal expansion). In a closed system the volume of water will grow when it is heated. As the volume 

of water grows there will be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause 

premature tank failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause 

intermittent Temperature-Pressure Relief Valve operation: water discharged from the valve due to excessive pressure build up. This 

condition is not covered under the limited warranty. The Temperature-Pressure Relief Valve is not intended for the constant relief of 

thermal expansion.
A properly sized and pressurized thermal expansion tank must be installed on all closed systems to control the harmful effects of 

thermal expansion. Contact a local plumbing service agency to have a thermal expansion tank installed.

AIR REQUIREMENTS

Carefully review the requirements for combustion and ventilation air in the Instruction Manual that came with the water heater. Failure to 

meet these requirements when the water heater is installed or overlooking their importance when servicing the water heater often 

results in needless down time, unnecessary parts replacement, and customer dissatisfaction.
An inadequate supply of air for combustion and ventilation often causes operational problems. A lack of combustion and ventilation air 

can create a negative ambient air pressure in the installed space which can lead to improper combustion and operational problems with 

pressure switches.

CONTAMINATED AIR

Combustion air that is contaminated can greatly diminish the life span of the water heater and water heater components such as 

Igniters and Burners. Propellants of aerosol sprays, beauty shop supplies, water softener chemicals and chemicals used in dry cleaning 

processes that are present in the combustion, ventilation or ambient air can cause such damage.
Vapors from volatile compounds such as solvents, cleaners, chlorine based chemicals and refrigerants in addition to being highly 

flammable in many cases, can also react to form highly corrosive substances such as acids inside the combustion chamber. The results 

can be hazardous and cause product failure.
If the water heater is installed in beauty shops, barber shops or laundries with dry cleaning equipment, it is imperative the water heater 

be installed in a Direct Vent configuration so that air for combustion is derived directly from the outdoor atmosphere through a sealed 

intake air pipe. See the venting installation section in the Instruction Manual that came with the water heater for more information on 

Direct Vent installations.

Содержание Cyclone XL 100 Series

Страница 1: ...ED BY A QUALIFIED SERVICE TECHNICIAN PRINTED 0220 100314732 2000568400 Rev A Service Handbook COMMERCIAL GAS WATER HEATERS COMMERCIAL GAS WATER HEATERS MODELS BTHS 750A 1000A SERIES 100 101 INSTALLATI...

Страница 2: ...21 13 Flow Switch Stuck Closed 22 VENTING 24 General Venting Information 24 INTAKE AIR CONNECTION 25 ELECTRICAL CONNECTIONS ALL MODELS 26 Power Fluctuations and Electrical Noise 26 Dedicated Power Wir...

Страница 3: ...procedures described in this service handbook If you do not understand the instructions given in this service handbook do not attempt to perform any procedures outlined in this service handbook SERVI...

Страница 4: ...charged from the valve due to excessive pressure build up This condition is not covered under the limited warranty The Temperature Pressure Relief Valve is not intended for the constant relief of ther...

Страница 5: ...e module The UIM includes the display circuit board and the control system s LCD Touch Display Used to adjust various user settings and view operational information 3 Central Control Board CCB enclosu...

Страница 6: ...red non sacrificial anode rods at the top Protective current is fed by the control system to the titanium electrodes at the end of each anode rod This current flows through the water to the conductive...

Страница 7: ...lation 35 Burner flange gasket 36 Observation sight glass 37 Burner 38 Flame rod 39 Flame rod gasket 40 Blower discharge gasket 41 Burner gasket 42 Spark rod 43 Spark rod gasket 44 Ignition cable 4 3...

Страница 8: ...View 1 Burner Blower Assembly 2 Blocked Intake Air switch 3 Powered anode rods 4 Temperature Pressure Relief Valve 5 2 NPT hot water outlet connection 6 Temperature Probe 7 Spark Ignition Control 8 12...

Страница 9: ...ivated Spark Ignition Transformer is energized 24 Volt Gas Valve is energized gas flows to Main Burner Is flame sensed at the Main Burner control system monitors the flame sensor Control System Locks...

Страница 10: ...supply pressures meet the requirements described above and listed in the table Failure of the gas supply to meet these requirements is not covered under the warranty High Pressure building supply syst...

Страница 11: ...he pressure port on the gas valve inlet flange See Figure 8 4 A digital manometer see Tools Recommended on Page 2 is needed to check supply gas pressure To monitor supply gas pressure attach a sensing...

Страница 12: ...ble The unit will begin an ignition cycle When the Gas Control Valve icon appears on display screen immediately look through the sight glass for a brief blue flame if you are getting an Ignition Failu...

Страница 13: ...e at the moment the gas control valve icon appears on the display follow these steps 1 Install a gas pressure gage at the gas valve s inlet pressure port and confirm that the gas supply pressure DOES...

Страница 14: ...0 hrs 0 mins ago Error Code A7 1201 Restriction in air intake Check intake pipe and termination for blockage Press the Advanced button for CAUSES The Blocked Air Intake Switch has detected a possible...

Страница 15: ...proper operation If flame is not present cycle the unit Off by turning the Enable Disable switch to Disable wait for 5 seconds and cycle the unit On by turning the Enable Disable switch to Enable to...

Страница 16: ...ycle the flame sensing current is normally greater than 8 0 A with a clean Flame Sensor Over time the Flame Sensor can degrade and this will reduce flame sensing current With heavier use more heating...

Страница 17: ...e replaced unless damaged The CCB monitors the current through the anodes and will declare a fault if there is a disconnected wire or if there is no water in the tank Side Mounted Power Anodes 2 Top M...

Страница 18: ...Replace the Temperature Probe if shorted resistance is below 390 Ohms See Temperature Probe section below TEMPERATURE PROBE This section of the Service Handbook provides information on the Temperatur...

Страница 19: ...n the UIM The electrical circuit breaker that serves the water heater must be turned off and on again to reset the Control System Note the Control System will not reset unless the condition has been c...

Страница 20: ...ter when replacing the Temperature Probe If the Control System continues to lock out displaying Energy Cut Out ECO on the UIM and the water temperature inside the water heater is becoming excessive at...

Страница 21: ...e exhaust temperature is normally around 100 F leaving the water heater If the heater is running during the standby mode the flue exhaust temperature tends moving up during the standby heating cycle T...

Страница 22: ...side the pump s outlet is installed correctly if it s a new heater installation Confirm the flow switch is installed vertically with flow arrow pointed upward Confirm the flow switch s vane can swing...

Страница 23: ...rm the flow switch is installed correctly with flow arrow vertically pointing upward 4 Remove inspect the flow switch s vane free from debris 5 Replace the flow switch if malfunction is detected with...

Страница 24: ...mbustion air from the room where they are installed and discharge all flue gases to the outdoor atmosphere through a sealed vent exhaust pipe Power vent configurations have one vent pipe connected to...

Страница 25: ...essure Port Figure 18 AIR INTAKE SCREEN Service Notes Plastic debris left on the edges of intake air pipe sections after cutting must be removed on Direct Vent installations This debris can collect in...

Страница 26: ...of local codes with the National Electrical Code ANSI NFPA 70 or the Canadian Electrical Code CSA C22 1 If any of the original wire as supplied on the water heater must be replaced it must be replaced...

Страница 27: ...still be energized and the display will read Water Heating Disabled The Enable Disable Switch can be used to disable operation and reset error codes To operate the water heater make sure the switch is...

Страница 28: ...imum equivalent lengths required in the Instruction Manual that came with the water heater Exceeding the maximum length or number of elbows allowed will also lead to Blocked Exhaust and or Blocked Air...

Страница 29: ...speeds during the Pre Post Purge operating states and runs at a lower speed during the Trial For Ignition operating state The Igniter Status icon is displayed on the UIM during the Trial For Ignition...

Страница 30: ...eed RPM Low Fire Speed RPM Ignition Speed RPM BTHS 750 4475 2300 2000 BTHS 1000 6000 2300 2000 Note 10 High Heating Speed RPMs are based from the Nominal Certification Heating Speed RPMs Table 3 Blowe...

Страница 31: ...e ignition cable from the spark igniter and the yellow wire from the Flame Sensor 9 Disconnect the 3 Pin and 5 Pin plugs from the Combustion Blower Assembly 10 Disconnect the 24 Volt power wires to th...

Страница 32: ...e 21 Burner Assembly The Control System is programmed to start sparking a few seconds before the Gas Control Valve opens See the Sequence of Operation Flow Chart page 9 Service Notes The animated ligh...

Страница 33: ...All instructions for ignition and temperature control originate from this circuit board Diagnostic and operational messages are generated by the CCB and sent to the UIM See Figure 24 page 40 Most of t...

Страница 34: ...RE 1 Ensure power to the water heater is turned off 2 Remove the water heater s top cover UIM and the bottom plastic cover 3 Remove the temperature probe connectors 4 Unlock clips on both sides and re...

Страница 35: ...J3 J13 J4 J17 J10 J9 J14 J15 J1 J6 J12 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 6 6 6 6 6 6 7 7 8 8 8 9 9 7 10 8 Figure 22 Central Contro...

Страница 36: ...9 Neutral J3 Socket UIM Pin DESCRIPTION 1 5V 2 AIN Reset 3 Data 4 Data 5 D Grd J4 Socket Flue Probe Flow Switch Pin DESCRIPTION 1 Flue Probe 2 Flue Probe 3 Flow switch 4 Flow Switch J5 Socket Blower...

Страница 37: ...t Used 6 Condensate 7 Gas Pressure Switch 8 Gas Pressure Switch 9 Gas Control Valve 10 Gas Control Valve 11 24V 12 24V Return J15 Socket Pressure Switches Table 14 Pin Table 15 Description 1 Blocked A...

Страница 38: ...the UIM Table 18 CPAM Fault Warning Codes Corrective Action Code Description Corrective Action Cc Anode Shorted Check wiring for shorts clean anode Ce Hardware fail ADC error Reset power if still fai...

Страница 39: ...s V 24V 24V Rtn Condensate Gas PS Gas V Switch 1 Red 2 Black CCB J6 120V Out Neutral 120 to Spark Red Black Red Black Upper Temperature Probe ECO 1 Red 2 Black CCB J9 Upper Probe ECO Thermistor 4 Red...

Страница 40: ...ser Interface Module Tank Temperature 103 F Operating Set Point 120 F Status Heating MENU HELP GAS OFF O N Figure 24 UIM User Interface Module Screen ICOMM REMOTE MONITORING SYSTEM This water heater i...

Страница 41: ...41 NOTES NOTES...

Страница 42: ...42 NOTES NOTES...

Страница 43: ...43 NOTES NOTES...

Страница 44: ...44 Tech Support 800 527 1953 Parts 800 433 2545 www hotwater com Copyright 2020 All rights reserved...

Отзывы: